Catalogue of duct walls
Verified by 1 conformance check against ASHRAE handbook: HVAC applications (SI edition): 1 in Industrial noise control.
Each catalogue has a page of its own: choose another one here and open it, or narrow the rows of this one by name and by the table that printed them.
Forty-six measurements of what the wall of a sheet metal duct does to the sound that crosses it, and the first thing to read on a row is which way it crossed. Breakout is the sound that leaves the duct through its wall, into the room the duct passes through. Break-in is the sound that enters the duct through the same wall and then travels along it to somewhere else. They are two different measurements of one wall and not two words for one number: the 305 mm by 305 mm duct in 24 gauge is 21 dB at 63 Hz on the way out and 16 dB on the way in, and 27 against 16 at 250 Hz. Two rows that differ only in direction are two rows here, and the column says which.
The rest of the row is what tells one duct from another. The shape is the chapter’s own word, which is why the breakout table says round where the break-in table says circular for the same geometry. The gauge is the US sheet metal gauge as printed, keeping the asterisk that marks a duct lined internally, and the note on those rows says what the lining is. The size is the two sides or the diameter, in millimetres; two rows carry a diameter the page prints once over three consecutive rows, so those two are marked as worked out rather than read. Several cells are a lower bound and not a value, because the sound radiated was below the background in the room the duct was measured in, and a bound is published as one.
Italic is a value this library worked out; a dotted underline is a cell that is not a plain number, and what it is reads on the cell; an asterisk is a note the page made about the row. Click a mark to read it, or give the table focus and press Enter to walk the marks with the arrow keys.
| Duct | Direction | Shape | Sheet gauge | Diameter mm | First side mm | Second side mm | Duct length m | 63 Hz dB | 125 Hz dB | 250 Hz dB | 500 Hz dB | 1 kHz dB | 2 kHz dB | 4 kHz dB | 8 kHz dB | Source |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 305 × 305 mm | breakout | rectangular | 24 | 305 | 305 | 21 | 24 | 27 | 30 | 33 | 36 | 41 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 305 × 610 mm | breakout | rectangular | 24 | 305 | 610 | 19 | 22 | 25 | 28 | 31 | 35 | 41 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 305 × 1220 mm | breakout | rectangular | 22 | 305 | 1 220 | 19 | 22 | 25 | 28 | 31 | 37 | 43 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 610 × 610 mm | breakout | rectangular | 22 | 610 | 610 | 20 | 23 | 26 | 29 | 32 | 37 | 43 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 610 × 1220 mm | breakout | rectangular | 20 | 610 | 1 220 | 20 | 23 | 26 | 29 | 31 | 39 | 45 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 1220 × 1220 mm | breakout | rectangular | 18 | 1 220 | 1 220 | 21 | 24 | 27 | 30 | 35 | 41 | 45 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 1220 × 2440 mm | breakout | rectangular | 18 | 1 220 | 2 440 | 19 | 22 | 25 | 29 | 35 | 41 | 45 | 45 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| Long Seam Ducts 200 mm The 63 Hz cell is printed “>45”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “(53)”. The only legend for that mark anywhere on folios 49.30 to 49.32 is the note under Table 32: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here. | breakout | round | 26 | 200 | 4.6 | > 45 | 53 | 55 | 52 | 44 | 35 | 34 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 350 mm The 63 Hz cell is printed “>50”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | breakout | round | 24 | 350 | 4.6 | > 50 | 60 | 54 | 36 | 34 | 31 | 25 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 560 mm The 63 Hz cell is printed “>47”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | breakout | round | 22 | 560 | 4.6 | > 47 | 53 | 37 | 33 | 33 | 27 | 25 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 810 mm The 63 Hz cell is printed “(51)”. The only legend for that mark anywhere on folios 49.30 to 49.32 is the note under Table 32: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here. | breakout | round | 22 | 810 | 4.6 | 51 | 46 | 26 | 26 | 24 | 22 | 38 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 300 mm The gauge carries the asterisk of the footnote printed under Table 30: “*Ducts internally lined with 25 mm thick 24 kg/m3 fiberglass with 0.6 mm perforated sheet metal inner liner.” (the page sets the 3 of the density as a superscript). | breakout | round | 26* | 300 | 3.6 | 52 | 51 | 53 | 51 | 50 | 46 | 36 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 610 mm | breakout | round | 24 | 610 | 7.3 | 51 | 53 | 51 | 44 | 36 | 26 | 29 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 610 mm The diameter cell is blank on the page, and the 610 mm this row serves is carried down from the row of its block that prints it rather than read from this row. The gauge carries the asterisk of the footnote printed under Table 30: “*Ducts internally lined with 25 mm thick 24 kg/m3 fiberglass with 0.6 mm perforated sheet metal inner liner.” (the page sets the 3 of the density as a superscript). | breakout | round | 24* | 610 | 7.3 | 51 | 51 | 54 | 44 | 39 | 33 | 47 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 610 mm The diameter cell is blank on the page, and the 610 mm this row serves is carried down from the row of its block that prints it rather than read from this row. The length is printed as a bare “3”, with no decimal, where every other length in Tables 30 and 32 carries one. The 63 Hz cell is printed “>48”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | breakout | round | 16 | 610 | 3 | > 48 | 53 | 36 | 32 | 32 | 28 | 41 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 915 mm | breakout | round | 20 | 915 | 7.3 | 51 | 51 | 52 | 46 | 36 | 32 | 55 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 305 × 152 mm | breakout | flat oval | 24 | 305 | 152 | 31 | 34 | 37 | 40 | 43 | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 610 × 152 mm | breakout | flat oval | 24 | 610 | 152 | 24 | 27 | 30 | 33 | 36 | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 610 × 305 mm | breakout | flat oval | 24 | 610 | 305 | 28 | 31 | 34 | 37 | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 1220 × 305 mm | breakout | flat oval | 22 | 1 220 | 305 | 23 | 26 | 29 | 32 | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 1220 × 610 mm | breakout | flat oval | 22 | 1 220 | 610 | 27 | 30 | 33 | — | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 2440 × 610 mm | breakout | flat oval | 20 | 2 440 | 610 | 22 | 25 | 28 | — | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 2440 × 1220 mm | breakout | flat oval | 18 | 2 440 | 1 220 | 28 | 31 | — | — | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 203 mm The 63 Hz cell is printed “>17”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “(31)”. The note printed under this table reads: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here. | break-in | circular | 26 | 203 | 4.57 | > 17 | 31 | 39 | 42 | 41 | 32 | 31 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 356 mm The 63 Hz cell is printed “>27”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 24 | 356 | 4.57 | > 27 | 43 | 43 | 31 | 31 | 28 | 22 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 559 mm The 63 Hz cell is printed “>28”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 22 | 559 | 4.57 | > 28 | 40 | 30 | 30 | 30 | 24 | 22 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Long Seam Ducts 813 mm The 63 Hz cell is printed “(35)”. The note printed under this table reads: “Parentheses indicate measurements in which background sound produced greater uncertainty than usual.” No hedge of this catalogue means that, and approximate is for a number an author rounded on purpose, so the number is held exactly as printed and the mark is recorded here. | break-in | circular | 22 | 813 | 4.57 | 35 | 36 | 23 | 23 | 21 | 19 | 35 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 203 mm The 63 Hz cell is printed “>20”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “>42”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 250 Hz cell is printed “>59”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 500 Hz cell is printed “>62”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 26 | 203 | 3.05 | > 20 | > 42 | > 59 | > 62 | 53 | 43 | 26 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 356 mm The 63 Hz cell is printed “>20”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “>36”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 26 | 356 | 3.05 | > 20 | > 36 | 44 | 28 | 31 | 32 | 22 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 660 mm The 63 Hz cell is printed “>27”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 24 | 660 | 3.05 | > 27 | 38 | 20 | 23 | 22 | 19 | 33 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 660 mm The 63 Hz cell is printed “>30”, a lower bound and not a value; the page gives no ceiling for it and none is invented. The 125 Hz cell is printed “>41”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 16 | 660 | 3.05 | > 30 | > 41 | 30 | 29 | 29 | 25 | 38 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| Spiral Wound Ducts 813 mm The 63 Hz cell is printed “>27”, a lower bound and not a value; the page gives no ceiling for it and none is invented. | break-in | circular | 22 | 813 | 3.05 | > 27 | 32 | 25 | 22 | 23 | 21 | 37 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 305 × 305 mm | break-in | rectangular | 24 | 305 | 305 | 16 | 16 | 16 | 25 | 30 | 33 | 38 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 305 × 610 mm | break-in | rectangular | 24 | 305 | 610 | 15 | 15 | 17 | 25 | 28 | 32 | 38 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 305 × 1220 mm | break-in | rectangular | 22 | 305 | 1 220 | 14 | 14 | 22 | 25 | 28 | 34 | 40 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 610 × 610 mm | break-in | rectangular | 22 | 610 | 610 | 13 | 13 | 21 | 26 | 29 | 34 | 40 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 610 × 1220 mm | break-in | rectangular | 20 | 610 | 1 220 | 12 | 15 | 23 | 26 | 28 | 36 | 42 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 1220 × 1220 mm | break-in | rectangular | 18 | 1 220 | 1 220 | 10 | 19 | 24 | 27 | 32 | 38 | 42 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 1220 × 2440 mm | break-in | rectangular | 18 | 1 220 | 2 440 | 11 | 19 | 22 | 26 | 32 | 38 | 42 | 42 | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | ||
| 305 × 152 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 24 | 305 | 152 | 18 | 18 | 22 | 31 | 40 | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 610 × 152 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 24 | 610 | 152 | 17 | 17 | 18 | 30 | 33 | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 610 × 305 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 24 | 610 | 305 | 15 | 16 | 25 | 34 | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 1220 × 305 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 22 | 1 220 | 305 | 14 | 14 | 26 | 29 | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 1220 × 610 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 22 | 1 220 | 610 | 12 | 21 | 30 | — | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 2440 × 610 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 20 | 2 440 | 610 | 11 | 22 | 25 | — | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) | |||
| 2440 × 1220 mm Table 34 is printed twice, complete, on folio 49.31 and again on folio 49.32. The two printings were compared row by row and agree, marks included, so one set of rows is kept. | break-in | flat oval | 18 | 2 440 | 1 220 | 19 | 28 | — | — | — | — | — | ASHRAE (2019) HVAC Applications Handbook Chapter 49 Tables 29 to 34, PDF pages 914-916 (printed pp. 49.30-49.32) |
References
Section titled “References”- American Society of Heating, Refrigerating and Air-Conditioning Engineers. (2019). ASHRAE handbook: HVAC applications (SI edition), Chapter 49, Noise and vibration control. ASHRAE. Chapter 49, Tables 29 to 34: the source of the rows of the catalogue of duct walls that cite it.