vibration.structural.building_damage

Effects of vibration on structures (DIN 4150-3:1999-02).

A pile driver, a passing tram or a blast puts vibration into the ground, and the question the neighbours ask is whether the building will crack. DIN 4150-3 answers it the way an engineering practice can afford to: not with a stress calculation, but with guideline values (Anhaltswerte) for one measured quantity, the peak particle velocity, drawn from a large body of measurements on real buildings. Keep under them and damage of the kind the standard defines has not been observed; exceed them and it does not follow that damage occurs, only that the cheap check no longer settles the question and Clauses 4.2 to 4.4 have to be done properly.

What is measured (5.1). At the foundation, the largest of the three components , , of the particle velocity, as a peak, each treated on its own; the standard calls it and then writes it . In the topmost floor plane, the larger of the two horizontal components, measured at the outside wall, which is the building’s horizontal answer to the foundation excitation rather than a new excitation.

Short-term vibration (Clause 5) is vibration that does not occur often enough for resonance to build up in the structure. Table 1 gives its guideline values by building class, and at the foundation they depend on frequency: a building tolerates a fast wiggle better than a slow one, so the value rises from 1 Hz to 100 Hz. Between the printed frequencies the guideline is read off Bild 1, which joins the corner values by straight lines on a linear frequency axis; above 100 Hz the 100 Hz value may be used. In the topmost floor plane one value covers all frequencies.

Long-term vibration (Clause 6, Dauererschütterungen) is the opposite case: often enough for the structure to respond at its own frequencies. Table 3 drops to a single value per class in the topmost floor plane, roughly a quarter of the short-term one, and prints no frequency dependence at all.

Buried pipelines (5.3) are judged on their own Table 2 by pipe material, measured on the pipe, and long-term vibration halves those values (6.3).

Three sizing rules travel with the tables and are here because a reader who has the tables needs them in the same breath:

  • Ceilings and floors (5.2) are separately covered by a vertical mm/s at the point of largest vibration, usually mid-span.
  • Massive engineering structures such as reinforced-concrete abutments and block foundations may take twice the row 1 values of Table 1 (5.1).
  • The lowest horizontal natural frequency of a building of five storeys or more is roughly with the storey count (6.4), which is the estimate that tells you whether the topmost floor plane will be excited at all. DIN 4150-1 prints it as Formula (4) and ISO 4866 in D.2, and story_fundamental_frequency is the one function for all three.

Clause 6.2 turns a measured velocity into a bending stress for a beam or a one-way slab vibrating in one mode, which is the bridge from this guideline check to the stress calculation of 4.2:

The guideline values are not limits in the legal sense and not an acceptance specification. They are where experience says the question stops being worth asking.

Auto-generated from the source docstrings by scripts/generate_api_docs.py (make api-docs). Do not edit by hand.

assess_building_vibration(
velocity_mm_s: float,
*,
building_class: Literal['commercial', 'residential', 'sensitive'],
frequency_hz: float | None = None,
location: Literal['foundation', 'top_floor'] = 'foundation',
duration: Literal['short_term', 'long_term'] = 'short_term',
massive_structure: bool = False,
) -> DamageAssessment

Compare one measured peak velocity with its guideline value.

Parameters

Name Description
velocity_mm_s The measured peak velocity, in millimetres per second; see DamageAssessment for which component it is. Zero is accepted and keeps to every guideline value.
building_class One of BUILDING_CLASSES. One of "commercial", "residential" or "sensitive".
frequency_hz Frequency of the dominant component, in hertz. Required for the short-term foundation case.
location "foundation" (default) or "top_floor".
duration "short_term" (default) or "long_term".
massive_structure See guideline_velocity.

Returns: The comparison, as a DamageAssessment.

Raises

Exception When
ValueError If the velocity is negative or not finite, or for any reason guideline_velocity raises.
TypeError if velocity_mm_s is not a single number, or building_class, duration or location is not a text. frequency_hz is refused the same way when it is not one real number.
bending_stress(
peak_velocity_m_s: float | np.floating[Any] | np.integer[Any],
*,
dynamic_modulus_pa: float,
density: float,
load_ratio: float = 1.0,
mode_factor: float = 1.0,
) -> float
bending_stress(
peak_velocity_m_s: Sequence[float] | Sequence[np.floating[Any]] | Sequence[np.integer[Any]] | NDArray[np.bool_ | np.integer[Any] | np.floating[Any]],
*,
dynamic_modulus_pa: float,
density: float,
load_ratio: float = 1.0,
mode_factor: float = 1.0,
) -> NDArray[np.float64]
bending_stress(
peak_velocity_m_s: NumericArrayLike,
*,
dynamic_modulus_pa: float,
density: float,
load_ratio: float = 1.0,
mode_factor: float = 1.0,
) -> float | NDArray[np.float64]

Peak bending stress from a peak velocity, Formula (1) of 6.2.

For a beam or a one-way slab of full rectangular section, constant stiffness and uniform mass, vibrating in one mode, the peak bending stress follows from the peak velocity alone:

The system dimensions do not enter, which is the point of the formula: a velocity measured where the amplitude is largest is enough. The mode factor lies between 1 and 1.3 in the technically important cases, so it moves the answer by less than a third.

Parameters

Name Description
peak_velocity_m_s Peak velocity over the beam length, in metres per second (scalar or array). Note the unit: the guideline tables are in millimetres per second and this formula is not.
dynamic_modulus_pa Dynamic modulus of elasticity , in pascals.
density Material density , in kilograms per cubic metre.
load_ratio The load coefficient , the beam’s own weight plus any uniformly distributed load it carries over its own weight. 1 for a beam carrying nothing else.
mode_factor The mode coefficient , dimensionless.

Returns: The peak bending stress, in pascals; a float for a number; an array for a sequence or an array, a zero-dimensional one included.

Raises

Exception When
ValueError If a material property, the load ratio or the mode factor is not positive and finite, or a velocity is negative.
TypeError if density, dynamic_modulus_pa, load_ratio or mode_factor is not a single number, or peak_velocity_m_s holds a text or a value that is not a real number.

Constant (float).

BENDING_STRESS_CONSTANT = 1.73

Constant (tuple).

BUILDING_CLASSES = ('commercial', 'residential', 'sensitive')

A DIN 4150-3 rule is used outside the range the standard offers it for.

Raised by story_fundamental_frequency below STORY_FREQUENCY_MIN_STORIES. The estimate is still returned: DIN 4150-3 6.4 offers 10 / n from about five storeys up, DIN 4150-1 Formula (4) for five and more, ISO 4866 D.2 for tall buildings, and below five none of them says anything, so the number is an extrapolation rather than the rule.

DamageAssessment(
velocity_mm_s: float,
building_class: Literal['commercial', 'residential', 'sensitive'],
location: Literal['foundation', 'top_floor'],
duration: Literal['short_term', 'long_term'],
frequency_hz: float | None,
*,
massive_structure: bool = False,
)

One measured velocity against the guideline value it is judged by.

Attributes

Name Description
velocity_mm_s The measured peak velocity, in millimetres per second: the largest of the three components at the foundation, or the larger of the two horizontal components in the topmost floor plane.
building_class The row of Table 1 or Table 3 that was used. One of "commercial", "residential" or "sensitive".
location Where the velocity was measured. One of "foundation" or "top_floor".
duration Which clause the guideline came from. One of "short_term" or "long_term".
frequency_hz The frequency the guideline was read at, or None where the guideline does not depend on frequency.
massive_structure Whether the row 1 values were raised by MASSIVE_STRUCTURE_FACTOR, the allowance 5.1 leaves to the assessor for a massive engineering structure.

The guideline value (guideline_mm_s) is read from Table 1 or Table 3 with those, so an assessment cannot be built against another value.

property

The guideline value the velocity is compared with, in mm/s.

DamageAssessment.plot(
ax: Axes | None = None,
*,
language: Literal['en', 'es'] = 'en',
**kwargs: Any,
) -> Axes

Draw Bild 1 with this measurement on it.

The three foundation curves of Table 1 against frequency, and the measured velocity as a point, so the margin is read rather than computed.

Requires matplotlib (the [plot] extra); returns the Axes.

Parameters

Name Description
ax Existing axes, or None to create a figure.
language Label language, "en" (default) or "es".
kwargs Forwarded to phonometry._plot.vibration.plot_damage_assessment.

property

The measured velocity as a fraction of the guideline value.

property

Whether the measured velocity keeps to the guideline value.

True is the whole of what the standard promises: damage of the kind 4.5 defines has not, in the experience the tables are drawn from, been observed. False is not the converse, and 5.1 says so: exceeding a guideline value does not mean damage occurs, it means the question has to be answered by 4.2 to 4.4 instead.

Constant (float).

FLOOR_VERTICAL_MM_S = 20.0

Constant (tuple).

FOUNDATION_FREQUENCIES_HZ = (1.0, 10.0, 50.0, 100.0)
foundation_guideline_curve(
building_class: Literal['commercial', 'residential', 'sensitive'],
frequency: NumericArrayLike | None = None,
) -> GuidelineCurve

Bild 1 as two arrays: frequency and guideline velocity.

The corner points of Table 1 by default, which is the polyline Bild 1 draws; pass frequency to sample the same polyline elsewhere.

Parameters

Name Description
building_class One of BUILDING_CLASSES. One of "commercial", "residential" or "sensitive".
frequency Frequency or frequencies to sample at, in hertz, or None for the four corners of Table 1.

Returns: The frequencies and the guideline velocities, as a GuidelineCurve.

Raises

Exception When
ValueError If the class is not one of the three, or a frequency is not positive and finite.
TypeError if building_class is not a text, or frequency holds a text or a value that is not a real number.
guideline_velocity(
building_class: Literal['commercial', 'residential', 'sensitive'],
frequency: float | np.floating[Any] | np.integer[Any] | None = None,
*,
location: Literal['foundation', 'top_floor'] = 'foundation',
duration: Literal['short_term', 'long_term'] = 'short_term',
massive_structure: bool = False,
) -> float
guideline_velocity(
building_class: Literal['commercial', 'residential', 'sensitive'],
frequency: Sequence[float] | Sequence[np.floating[Any]] | Sequence[np.integer[Any]] | NDArray[np.bool_ | np.integer[Any] | np.floating[Any]],
*,
location: Literal['foundation', 'top_floor'] = 'foundation',
duration: Literal['short_term', 'long_term'] = 'short_term',
massive_structure: bool = False,
) -> NDArray[np.float64]
guideline_velocity(
building_class: Literal['commercial', 'residential', 'sensitive'],
frequency: NumericArrayLike | None = None,
*,
location: Literal['foundation', 'top_floor'] = 'foundation',
duration: Literal['short_term', 'long_term'] = 'short_term',
massive_structure: bool = False,
) -> float | NDArray[np.float64]

The guideline peak velocity of Table 1 or Table 3, in mm/s.

At the foundation for short-term vibration the guideline is a function of frequency, read off Bild 1: constant below 10 Hz, then two straight segments joining the corner values of Table 1 on a linear frequency axis, and constant again above 100 Hz, since 5.1 allows the 100 Hz value to be used for anything faster. Everywhere else Table 1 and Table 3 print one number for all frequencies, and frequency is then not needed.

Parameters

Name Description
building_class One of BUILDING_CLASSES. One of "commercial", "residential" or "sensitive".
frequency Frequency of the dominant component, in hertz (scalar or array). Required for the short-term foundation case, and refused for every other one, where the printed value is the same at every frequency and a frequency would govern nothing.
location "foundation" (default) or "top_floor".
duration "short_term" (Table 1, default) or "long_term" (Table 3).
massive_structure Raise the row 1 values by MASSIVE_STRUCTURE_FACTOR, which is the most 5.1 allows a massive engineering structure. The allowance is written for row 1 of Table 1 alone, so it applies to the commercial class and to short-term vibration, and is refused anywhere else.

Returns: The guideline peak velocity, in millimetres per second: a float without a frequency or for a number; an array for a sequence or an array, a zero-dimensional one included.

Raises

Exception When
ValueError If a name is not one of its choices, if the short-term foundation case is asked for without a frequency, if a frequency is given for a case that does not read one, if a frequency is not positive and finite, or if massive_structure is asked for outside row 1 of Table 1.
TypeError if building_class, duration or location is not a text, or frequency holds a text or a value that is not a real number.
GuidelineCurve(
frequencies: NDArray[np.float64],
velocities_mm_s: NDArray[np.float64],
)

A guideline velocity polyline of DIN 4150-3 Bild 1, sampled.

What foundation_guideline_curve returns: the frequencies and the guideline velocities, named, where a (frequency_hz, guideline_mm_s) tuple used to be unpacked by position.

Attributes

Name Description
frequencies The frequencies, in hertz.
velocities_mm_s The guideline velocity at each, in mm/s.

Constant (mapping).

LONG_TERM_TOP_FLOOR_MM_S = {'commercial': 10.0, 'residential': 5.0, 'sensitive': 2.5}

Constant (float).

MASSIVE_STRUCTURE_FACTOR = 2.0
pipeline_guideline_velocity(
material: Literal['welded_steel', 'concrete_or_flanged_metal', 'masonry_or_plastic'],
*,
duration: Literal['short_term', 'long_term'] = 'short_term',
) -> float

The guideline peak velocity on a buried pipeline (Table 2), in mm/s.

Measured on the pipe itself; a substitute measurement at the ground surface above it only estimates the value (5.3, D.1). Long-term vibration halves the table, which is what 6.3 allows without further evidence.

Parameters

Name Description
material One of PIPELINE_MATERIALS. One of "welded_steel", "concrete_or_flanged_metal" or "masonry_or_plastic".
duration "short_term" (default) or "long_term".

Returns: The guideline peak velocity, in millimetres per second.

Raises

Exception When
ValueError If a name is not one of its choices.
TypeError if duration or material is not a text.

Constant (float).

PIPELINE_LONG_TERM_FACTOR = 0.5

Constant (tuple).

PIPELINE_MATERIALS = ('welded_steel', 'concrete_or_flanged_metal', 'masonry_or_plastic')

Constant (mapping).

PIPELINE_MM_S = {'welded_steel': 100.0, 'concrete_or_flanged_metal': 80.0, 'masonry_or_plastic': 50.0}

Constant (mapping).

SHORT_TERM_FOUNDATION_MM_S = {'commercial': (20.0, 20.0, 40.0, 50.0), 'residential': (5.0, 5.0, 15.0, 20.0), 'sensitive': (3.0, 3.0, 8.0, 10.0)}

Constant (mapping).

SHORT_TERM_TOP_FLOOR_MM_S = {'commercial': 40.0, 'residential': 15.0, 'sensitive': 8.0}

Constant (int).

STORY_FREQUENCY_MIN_STORIES = 5

Constant (float).

STORY_FREQUENCY_NUMERATOR_HZ = 10.0
story_fundamental_frequency(n_stories: int | np.integer[Any]) -> float

The rough lowest horizontal natural frequency of a building.

f ~ 10 / n, offered for buildings from about five storeys up. Three documents print the same estimate: DIN 4150-3:1999-02 6.4 (the Stockwerkgleichung, from about five storeys), DIN 4150-1:2001-06 Formula (4) (five storeys and more) and ISO 4866:2010 D.2 (the simplest of the empirical formulae for tall buildings), so this is the one function for all three. It is a rough estimate and the standards say so; its use is to tell whether the excitation is anywhere near the frequency at which the topmost floor plane will answer.

Parameters

Name Description
n_stories The number of storeys n.

Returns: The estimated lowest horizontal natural frequency, in hertz.

Raises

Exception When
TypeError If n_stories is a bool, a text or an array rather than a number.
ValueError If the storey count is not a whole number of at least 1.

Warns

Warning When
BuildingDamageWarning Below STORY_FREQUENCY_MIN_STORIES, where the estimate is an extrapolation of a rule the standard offers for taller buildings.