building.prediction.simplified_model

Building acoustic performance prediction (EN 12354-1/-2:2000).

This is the prediction counterpart of the measurement modules (phonometry.building.measurement.laboratory_insulation for laboratory R/Ln and phonometry.building.measurement.insulation for field R'/L'n). EN 12354 estimates the in-situ apparent performance of a building from the laboratory performance of its elements, adding the flanking transmission that a field measurement would capture but a laboratory measurement suppresses.

Both parts have a detailed per-band model and a simplified single-number model. This module implements the simplified single-number model (Part 1 Clause 4.4, Part 2 Clause 4.3): it takes the weighted single-number ratings of the elements (Rw of walls/floors, ΔRw/ΔLw of linings/coverings and the Kij vibration-reduction indices of the junctions) and predicts the apparent weighted rating (R'w airborne, L'n,w impact). The simplified model is exact for RA and a good approximation for R'w (Part 1 Clause 4.4.1), with a reported standard deviation of about 2 dB (Clause 5).

Airborne, Formula (26). The apparent weighted sound reduction index is the energetic sum of the direct path Dd and, for every flanking element, the three flanking paths Ff, Df and Fd:

with the direct path (Formula 27) and each flanking path (Formula 28a)

where m is the reference coupling length.

Junctions, Annex E. The vibration reduction index Kij of rigid cross (E.3) and T (E.4) junctions, junctions with flexible interlayers (E.5), lightweight façade junctions (E.6), junctions of lightweight double-leaf walls with homogeneous elements (E.7) or with other coupled double-leaf walls (E.8), and corners / thickness changes (E.9) are empirical functions of the mass ratio . A minimum value Kij,min follows from the Kij,min relation of Clause 4.4.2 (printed as Eq. (23) in the BS EN 12354-1:2000 edition).

Impact, Formula (21). with the bare-floor equivalent level Ln,w,eq (Annex B ), the covering improvement ΔLw (ISO 717-2) and the flanking correction K from Table 1.

Clause citations refer to EN 12354-1:2000 (airborne) or EN 12354-2:2000 (impact).

Auto-generated from the source docstrings by scripts/generate_api_docs.py (make api-docs). Do not edit by hand.

AirbornePredictionResult(
r_prime_w: float,
r_direct_w: float,
paths: tuple[PathContribution, ...],
dominant: PathContribution,
)

Predicted apparent airborne insulation (EN 12354-1:2000, Formula 26).

Attributes

Name Description
r_prime_w Apparent weighted sound reduction index R'w, in dB.
r_direct_w Direct-path weighted index RDd,w, in dB (Formula 27).
paths Per-path contributions in input order (direct path first, then the flanking paths as supplied), each with its share of the energy.
dominant The path carrying the most energy (PathContribution).
AirbornePredictionResult.plot(
ax: Axes | None = None,
*,
language: Literal['en', 'es'] = 'en',
**kwargs: Any,
) -> Axes

Plot the per-path shares of the transmitted energy.

Requires matplotlib (the [plot] extra); returns the Axes.

Parameters

Name Description
language The language of the labels: "en" or "es".
AirbornePredictionResult.report(
path: str | os.PathLike[str],
*,
metadata: ReportMetadata | None = None,
engine: Literal['reportlab'] = 'reportlab',
verbose: bool = False,
language: Literal['en', 'es'] = 'en',
) -> str

Render a predicted airborne insulation report to a PDF (EN 12354-1).

Writes a one-page prediction report for the predicted apparent sound reduction index R' between rooms estimated by the EN/ISO 12354-1:2000 simplified single-number model (Clause 4.4): a standard-basis line that states the sheet is a prediction from element data and not a measurement, an optional metadata header block, a two-panel body with the transmission-path table (the direct path and each flanking path’s weighted index Rij,w) beside the per-path share-of-energy plot, the boxed predicted rating R'w, the prediction statement (with the model’s ~2 dB standard deviation) and, when a requirement is supplied, a PASS/FAIL verdict (the apparent index passes at or above the requirement), followed by a footer.

The applicable ReportMetadata fields describe the predicted situation: specimen (the separating element), area (the separating-element area Ss), source_volume / receiving_volume (the room geometry), client, manufacturer, test_room, laboratory (the calculator / laboratory), operator, report_id and test_date. A summary of the flanking construction and the model assumptions is recorded in notes (free text), and requirement supplies the target R'w.

Parameters

Name Description
path Destination path of the PDF file.
metadata Optional ReportMetadata; None produces a lightweight fiche (body, rating, statement, disclaimer).
engine Rendering back end; only "reportlab" is supported.
verbose When True, the path table also shows each path’s share of the transmitted sound energy.
language Fiche language: "en" (default) or "es".

Returns: The written path as a str.

Raises

Exception When
ValueError If engine is unknown or language is not supported.
ImportError If reportlab is not installed (the [report] extra), or matplotlib is missing for the embedded figure (the [plot] extra).

A building prediction read outside the range its relation is stated for.

Emitted when the bare-floor equivalent impact level of EN 12354-2 Annex B is asked for a mass per unit area outside 100 kg/m² to 600 kg/m², and when a lining of ISO 12354-1:2017 Annex D is rated at a resonance frequency or on a base rating outside the ranges Table D.1 and Clause D.2.2 state. The number is still returned: it is the printed relation extrapolated, which the standard does not cover.

combined_lining_improvement(delta_a: float, delta_b: float) -> float

Combine two lining improvements (EN 12354-1 Formulas 30/31).

For two linings the total improvement is the larger value plus half the smaller: . For a single lining pass the other as 0.

Parameters

Name Description
delta_a Improvement of the first lining, in dB.
delta_b Improvement of the second lining, in dB.

Returns: Combined ΔR/ΔRij, in dB.

Raises

Exception When
TypeError if delta_a or delta_b is not a single number.
equivalent_impact_level(mass_per_area: float) -> float

Bare-floor equivalent weighted impact level Ln,w,eq (Part 2, Annex B).

with kg/m², the closed form used in the Annex E worked example for a homogeneous concrete floor. The Annex B relation is stated for homogeneous floors of 100 kg/m² to 600 kg/m²; outside that envelope the value is an extrapolation and a BuildingPredictionWarning is emitted.

Parameters

Name Description
mass_per_area Mass per unit area m' of the bare floor, in kg/m² (must be positive; the Annex B relation covers 100-600 kg/m²).

Returns: Ln,w,eq, in dB.

Raises

Exception When
ValueError If mass_per_area is not positive.
TypeError if mass_per_area is not a single number.

Warns

Warning When
BuildingPredictionWarning If mass_per_area lies outside the 100-600 kg/m² the relation is stated for.
flanking_element(
*,
label: str,
r_flanking: float,
r_separating: float,
k_ff: float,
k_fd: float,
k_df: float,
separating_area: float,
coupling_length: float,
delta_r_ff: float = 0.0,
delta_r_fd: float = 0.0,
delta_r_df: float = 0.0,
flanking_area: float | None = None,
) -> tuple[FlankingPath, FlankingPath, FlankingPath]

Build the three flanking paths (Ff, Df, Fd) of one flanking element.

Convenience wrapper over flanking_path for the common case where a flanking element is essentially the same on the source and receiving side (Clause 4.4.1). Returns the Ff, Df and Fd paths that this element contributes across its junction with the separating element.

Kij,min (Clause 4.4.2). When flanking_area is given, the mandatory floor is applied automatically per path: KFf is clamped to (both junction elements are the flanking element) and KFd/KDf to (flanking and separating element), via junction_min_vibration_reduction. Without flanking_area the per-path floors cannot be formed from the available geometry, so the raw k_ff/k_fd/k_df are used unchanged; compute the floors yourself (or call flanking_path with kij_min) in that case to stay within Clause 4.4.2.

Parameters

Name Description
label Base name; paths are labelled "<label>-Ff" etc.
r_flanking Weighted sound reduction index of the flanking element.
r_separating Weighted sound reduction index of the separating element.
k_ff KFf vibration reduction index, in dB.
k_fd KFd vibration reduction index, in dB.
k_df KDf vibration reduction index, in dB.
separating_area Separating-element area Ss, in m².
coupling_length Junction coupling length lf, in m.
delta_r_ff Combined lining improvement for the Ff path, in dB.
delta_r_fd Combined lining improvement for the Fd path, in dB.
delta_r_df Combined lining improvement for the Df path, in dB.
flanking_area Flanking-element area , in m². Enables the automatic Kij,min clamp (Clause 4.4.2); None skips it.

Returns: The (Ff, Df, Fd) FlankingPath triple.

Raises

Exception When
ValueError If a geometry value is not positive or an input is non-finite.
TypeError if coupling_length, delta_r_df, delta_r_fd, delta_r_ff, flanking_area, k_df, k_fd, k_ff, r_flanking, r_separating or separating_area is not a single number.
flanking_path(
*,
label: str,
kind: Literal['Ff', 'Df', 'Fd'],
r_source: float,
r_receive: float,
k_ij: float,
separating_area: float,
coupling_length: float,
delta_r: float = 0.0,
kij_min: float | None = None,
) -> FlankingPath

Build one flanking path Rij,w (EN 12354-1 Formula 28a).

with r_source and r_receive as / , delta_r as and k_ij as . The two element indices depend on the path: for Ff both are the flanking element (RF,w, Rf,w); for Fd they are the flanking (source) and separating (receive) elements; for Df the separating (source) and flanking (receive) elements.

When kij_min is given, k_ij is clamped up to it (max(k_ij, kij_min)) before the path is formed, enforcing the floor of Clause 4.4.2 (compute kij_min with junction_min_vibration_reduction). Left as None the raw k_ij is used unchanged.

Parameters

Name Description
label Human-readable path name.
kind "Ff", "Df" or "Fd".
r_source Weighted sound reduction index of the source-side element.
r_receive Weighted sound reduction index of the receive-side element.
k_ij Vibration reduction index of this path, in dB.
separating_area Area Ss of the separating element, in m².
coupling_length Junction coupling length lf, in m.
delta_r Combined lining improvement ΔRij,w for this path, in dB.
kij_min Optional Kij,min floor (Clause 4.4.2); k_ij is raised to it when it lies below. None disables the clamp.

Returns: The FlankingPath.

Raises

Exception When
ValueError If kind is unknown, areas/lengths are not positive, or any value is non-finite.
TypeError if coupling_length, delta_r, k_ij, kij_min, r_receive, r_source or separating_area is not a single number, or kind is not a text.
FlankingPath(*, label: str, kind: Literal['Ff', 'Df', 'Fd'], r_ij_w: float)

One flanking transmission path (Ff, Df or Fd) of the simplified model.

Attributes

Name Description
label Human-readable path name, e.g. "floor-Ff".
kind Path type, one of "Ff", "Df", "Fd".
r_ij_w Weighted flanking sound reduction index Rij,w of the path, in dB (EN 12354-1 Formula 28a).
impact_flanking_correction(
separating_mass: float,
flanking_mass: float,
) -> int

Flanking correction K from Table 1 (EN 12354-2:2000).

Looks up K (dB) for the separating-floor mass and the mean mass of the homogeneous flanking elements, selecting the nearest tabulated row/column (the table is discrete; masses outside 100–900 / 100–500 kg/m² clamp to the nearest edge).

Parameters

Name Description
separating_mass Mass per unit area of the separating floor, in kg/m².
flanking_mass Mean mass per unit area of the homogeneous flanking elements not covered by additional layers, in kg/m².

Returns: The correction K, in dB (a non-negative integer).

Raises

Exception When
ValueError If a mass is not positive.
TypeError if flanking_mass or separating_mass is not a single number.
ImpactPredictionResult(
l_prime_n_w: float,
ln_w_eq: float,
delta_l_w: float,
k_correction: float,
)

Predicted apparent impact insulation (EN 12354-2:2000, Formula 21).

Attributes

Name Description
l_prime_n_w Apparent weighted normalized impact sound pressure level L'n,w, in dB.
ln_w_eq Bare-floor equivalent weighted level Ln,w,eq, in dB.
delta_l_w Weighted covering improvement ΔLw, in dB.
k_correction Flanking correction K, in dB (Table 1).
ImpactPredictionResult.plot(
ax: Axes | None = None,
*,
language: Literal['en', 'es'] = 'en',
**kwargs: Any,
) -> Axes

Plot the Formula 21 terms and the resulting L'n,w.

Requires matplotlib (the [plot] extra); returns the Axes.

Parameters

Name Description
language The language of the labels: "en" or "es".
ImpactPredictionResult.report(
path: str | os.PathLike[str],
*,
metadata: ReportMetadata | None = None,
engine: Literal['reportlab'] = 'reportlab',
verbose: bool = False,
language: Literal['en', 'es'] = 'en',
) -> str

Render a predicted impact insulation report to a PDF (EN 12354-2).

Writes a one-page prediction report for the predicted apparent normalized impact sound pressure level L'n estimated by the EN/ISO 12354-2:2000 simplified single-number model (Clause 4.3): a standard-basis line that states the sheet is a prediction from element data and not a measurement, an optional metadata header block, a two-panel body with the Formula (21) term table (the bare-floor equivalent level Ln,w,eq, the covering improvement ΔLw and the flanking correction K) beside the term plot, the boxed predicted rating L'n,w, the prediction statement (with the model’s ~2 dB standard deviation) and, when a requirement is supplied, a PASS/FAIL verdict (the apparent level passes at or below the requirement, a lower impact level being better), followed by a footer.

The applicable ReportMetadata fields describe the predicted situation: specimen (the separating floor), area (the floor area), mass_per_area (the bare floor’s mass per unit area), receiving_volume (the receiving-room geometry), client, manufacturer, test_room, laboratory (the calculator / laboratory), operator, report_id and test_date. A summary of the flanking construction and the model assumptions is recorded in notes (free text), and requirement supplies the target L'n,w.

Parameters

Name Description
path Destination path of the PDF file.
metadata Optional ReportMetadata; None produces a lightweight fiche (body, rating, statement, disclaimer).
engine Rendering back end; only "reportlab" is supported.
verbose Accepted for a uniform .report() signature; the impact fiche has a single body layout, so it has no effect.
language Fiche language: "en" (default) or "es".

Returns: The written path as a str.

Raises

Exception When
ValueError If engine is unknown or language is not supported.
ImportError If reportlab is not installed (the [report] extra), or matplotlib is missing for the embedded figure (the [plot] extra).
junction_min_vibration_reduction(
coupling_length: float,
s_i: float,
s_j: float,
) -> float

Minimum vibration reduction index Kij,min (EN 12354-1 Clause 4.4.2).

Printed as Formula (29) in the EN 12354-1:2000 edition.

with the reference coupling length m. When the tabulated Kij is below this value, the minimum is used (Clause 4.4.2).

Parameters

Name Description
coupling_length Common coupling length lf of the junction, in m.
s_i Area of element i, in m².
s_j Area of element j, in m².

Returns: Kij,min, in dB.

Raises

Exception When
ValueError If any argument is not positive.
TypeError if coupling_length, s_i or s_j is not a single number.
junction_vibration_reduction(
junction_type: Literal['rigid_cross', 'rigid_t', 'flexible_t', 'lightweight_facade', 'lightweight_double_homogeneous', 'lightweight_double_coupled', 'corner', 'thickness_change'],
path: Literal['through', 'corner', 'double_leaf'],
mass_ratio: float,
*,
frequency: float = 500.0,
f1: float = 125.0,
) -> float

Vibration reduction index Kij of a junction (EN 12354-1 Annex E).

Empirical Kij for common junctions as a function of the mass ratio (Formula E.2), where mass_ratio is , the mass per unit area of the perpendicular element over that of the element carrying the path. path selects the through branch (in-line elements, K13), the corner branch () or, for double-leaf separating walls, the double-leaf branch (K24, the path between the two flanking legs across the double leaf).

Supported junction_type values and their formulas:

  • "rigid_cross" (E.3): through ; corner .
  • "rigid_t" (E.4): through ; corner .
  • "flexible_t" (E.5, wall junction with flexible interlayers): through ; corner with for (else 0) and Hz for the typical interlayer MN/m³; double-leaf clamped to dB. (The 2000 print states the clamp as “0 ≤ K24 ≤ −4 dB”, an obvious misprint of the bounds’ order.)
  • "lightweight_facade" (E.6): through ; corner .
  • "lightweight_double_homogeneous" (E.7, lightweight double-leaf wall joined to homogeneous elements): through ; corner ; double-leaf with Hz. The K24 path is carried by the homogeneous element crossing the double leaf, so its per-path mass_ratio is leaf-over-homogeneous and the validity condition (homogeneous over three times heavier than a leaf) reads mass_ratio . (The 2000 print states this line as in the figure-axis variable of Figure E.9, contradicting the annex’s own per-path definition of M; both forms are numerically identical, and ISO 12354-1:2017 E.3.5 prints the per-path form implemented here. See docs/ERRATA.md.)
  • "lightweight_double_coupled" (E.8, junction of lightweight coupled double-leaf walls): through ; corner ; with Hz.
  • "corner" (E.9 A, two elements meeting at a corner): corner (); the only path.
  • "thickness_change" (E.9 B, thickness change in an element): through (); the only path.

Parameters

Name Description
junction_type Junction geometry (see above). One of "rigid_cross", "rigid_t", "flexible_t", "lightweight_facade", "lightweight_double_homogeneous", "lightweight_double_coupled", "corner" or "thickness_change".
path "through" (K13; also the single K12 path of a thickness change), "corner" (K12 = K23; also the single path of a corner) or "double_leaf" (K24).
mass_ratio , the mass per unit area of the perpendicular element over that of the element carrying the path (must be positive). The same per-path convention applies to every branch, including both double_leaf (K24) branches.
frequency Frequency at which Kij is evaluated, in Hz; only the "flexible_t" (through/corner) and the E.7/E.8 lightweight double-leaf junctions are frequency dependent. Defaults to 500 Hz, the value used by the simplified model (Clause 4.4.2), at which the E.7/E.8 terms vanish.
f1 Interlayer characteristic frequency for "flexible_t", in Hz.

Returns: Kij, in dB.

Raises

Exception When
ValueError If mass_ratio is not positive, frequency/f1 are not positive, an unknown junction_type/path is given, the requested path does not exist for the junction, or the E.7 double-leaf branch is requested outside its validity.
TypeError if f1, frequency or mass_ratio is not a single number, or junction_type or path is not a text.
PathContribution(
label: str,
kind: Literal['Dd', 'Ff', 'Df', 'Fd'],
r_w: float,
energy_fraction: float,
)

A transmission path with its share of the total transmitted energy.

Attributes

Name Description
label Path name ("Dd" for the direct path).
kind "Dd", "Ff", "Df" or "Fd".
r_w Weighted sound reduction index of the path, in dB.
energy_fraction Fraction of the total transmitted sound energy carried by this path (0 to 1); the dominant path has the largest.
predicted_airborne_insulation(
*,
r_direct: float,
flanking_paths: Sequence[FlankingPath] = (),
delta_r_direct: float = 0.0,
) -> AirbornePredictionResult

Predict the apparent airborne insulation R'w (EN 12354-1 Formula 26).

Energetically combines the direct path (Formula 27, from r_direct and delta_r_direct) with the supplied flanking paths:

With no flanking paths the result equals the direct path RDd,w; each added path strictly lowers R'w. The result exposes every path’s share of the transmitted energy so the dominant path is visible.

Parameters

Name Description
r_direct Weighted sound reduction index of the separating element Rs,w, in dB.
flanking_paths Flanking paths (see flanking_element). May be empty for the direct-only case.
delta_r_direct Combined lining improvement ΔRDd,w on the separating element, in dB.

Returns: The AirbornePredictionResult.

Raises

Exception When
ValueError If any input is non-finite.
TypeError if delta_r_direct or r_direct is not a single number.
predicted_impact_insulation(
*,
ln_w_eq: float,
delta_l_w: float = 0.0,
k_correction: float = 0.0,
) -> ImpactPredictionResult

Predict the apparent impact insulation L'n,w (EN 12354-2 Formula 21).

. The bare-floor equivalent level may come from equivalent_impact_level and the flanking correction from impact_flanking_correction.

Parameters

Name Description
ln_w_eq Bare-floor equivalent weighted level Ln,w,eq, in dB.
delta_l_w Weighted covering improvement ΔLw (ISO 717-2), in dB.
k_correction Flanking correction K (Table 1), in dB.

Returns: The ImpactPredictionResult.

Raises

Exception When
ValueError If any input is non-finite.
TypeError if delta_l_w, k_correction or ln_w_eq is not a single number.
standardized_impact_level(l_prime_n_w: float, volume: float) -> float

Standardized apparent impact level L'nT,w (EN 12354-2 Formula 3).

with m² and s, the exact Formula (3) form. The standard’s own Annex E.3 worked example rounds the factor to (), 0.18 dB below the exact form; both round to the same integer rating in E.3.

Parameters

Name Description
l_prime_n_w Apparent weighted normalized impact level L'n,w, dB.
volume Receiving-room volume V, in m³ (must be positive).

Returns: L'nT,w, in dB.

Raises

Exception When
ValueError If volume is not positive.
TypeError if l_prime_n_w or volume is not a single number.
standardized_level_difference(
r_prime_w: float,
volume: float,
separating_area: float,
) -> float

Standardized level difference DnT,w from R'w (EN 12354-1 Formula 5b).

with s, the exact Formula (5b) form, applied to the weighted single numbers of the simplified model (Clause 4.4). The Annex H.3 worked example rounds the factor to (), printing dB where the exact form gives 53.6 dB; both round to the same dB.

Parameters

Name Description
r_prime_w Apparent weighted sound reduction index R'w, in dB (see predicted_airborne_insulation).
volume Receiving-room volume V, in m³ (must be positive).
separating_area Separating-element area Ss, in m² (must be positive).

Returns: DnT,w, in dB.

Raises

Exception When
ValueError If volume or separating_area is not positive.
TypeError if r_prime_w, separating_area or volume is not a single number.