# Sound Absorption Measurement and Rating

> One page of the phonometry documentation, as Markdown. Index: https://docs.jmrp.io/phonometry/llms.txt

Canonical: https://docs.jmrp.io/phonometry/materials/absorbers/absorption-measurement/
Language: en
Alternate: https://docs.jmrp.io/phonometry/es/materials/absorbers/absorption-measurement/index.md
Version: phonometry 4.0.0
Install: pip install "phonometry[full]"
Author: José Manuel Requena Plens (https://orcid.org/0000-0003-1250-6212)
Published: 2026-07-28
Updated: 2026-11-16T21:36:13Z
Standards: ISO 354:2003; ISO 11654:1997; ISO 12999-2:2020
Verified: 9 conformance checks (ISO 354:2003; ISO 11654:1997; ISO 12999-2:2020) https://docs.jmrp.io/phonometry/reference/conformance/
License: MIT (https://github.com/jmrplens/phonometry/blob/main/LICENSE)
Summary: Sound absorption in a reverberation room (ISO 354), its rating as alpha_w with a class (ISO 11654) and the uncertainty of both (ISO 12999-2).

---

Of all the numbers a materials laboratory produces, the sound-absorption
coefficient is the one that travels furthest: it leaves the reverberation room
on a datasheet, enters a Sabine estimate, an EN 12354-6 absorption budget or a
public-tender requirement, and is rarely questioned again. This guide covers
that number's whole laboratory life. The **measurement** is ISO 354: a sample
of 10 m² to 12 m² on the floor of a reverberation room, two decay times, and
Sabine's formula run backwards to get the random-incidence coefficient
$\alpha_\mathrm{s}$ per one-third-octave band. The **rating** is ISO 11654: the spectrum
collapsed into the weighted coefficient $\alpha_\mathrm{w}$ with its letter class A to
E, the single number absorber datasheets quote. And because a coefficient
without an uncertainty is only half a result, ISO 12999-2 supplies the
**measurement uncertainty** of both. The normal-incidence counterpart measured
on small samples lives in the [impedance tube](https://docs.jmrp.io/phonometry/materials/absorbers/impedance-tube/)
guide; the closing section here, after the uncertainty, explains when each of
the two is the right tool and why the two numbers do not match.

## 1. Reverberation-room measurement (ISO 354)

![Plan of an ISO 354 reverberation room with non-parallel walls: the 10.8 square metre rectangular specimen on the floor with its edges deliberately not parallel to the room edges and a 0.75 metre clearance dimensioned to the nearest boundary, three microphone positions and two loudspeaker positions with their separation rules, suspended diffuser panels near the ceiling, an inset showing the empty room giving T1 and A1 above the room with the specimen giving T2 and A2, and a strip comparing the Type A and Type E-400 mountings in section](https://docs.jmrp.io/phonometry/media/diagram_iso354_room.svg)

The reverberation-room measurement itself is `measure_sound_absorption`. It
takes the one-third-octave reverberation time of the empty room ($T_1$) and of
the room with the specimen installed ($T_2$), the room volume $V$ and the
specimen area $S$, and returns a frozen `SoundAbsorptionMeasurement`. The
equivalent sound absorption areas follow from Sabine's equation (ISO 354:2003
Eqs. (5) and (7)), and the coefficient from their difference (Eqs. (8)/(9)):

$$
A = \frac{55.3\ V}{c\ T} - 4 V m, \qquad
\alpha_\mathrm{s} = \frac{A_2 - A_1}{S}, \qquad c = 331 + 0.6\ t ,
$$

with $c$ the speed of sound built from the room air temperature $t$ in °C
(Eq. (6), valid 15–30 °C) and $m$ the power attenuation coefficient of air in
1/m. The coefficient may exceed 1.0 from edge and diffraction effects
(Clause 3.7 NOTE 2) and is never clamped; the
[closing section](#tube-or-reverberation-room) explains why.

**The air-attenuation term $m$, and why the default 0 is not a shortcut.**
$\alpha_\mathrm{s}$ is a *difference* of two absorption areas, so a single $m$ enters
$A_1$ and $A_2$ identically and the $-4Vm$ term cancels exactly:
`measure_sound_absorption` broadcasts one $m$ into both, and the default
$m = 0$ therefore changes nothing as long as both decays were measured under
the same climate. Only the difference $m_2 - m_1$ survives, which is why
Clause 6.3.2 asks for $T_1$ and $T_2$ to be measured at almost the same
temperature and relative humidity, inside $30\ \% \le \text{RH} \le 90\ \%$
and $t \ge 15$ °C throughout the test. The term itself is anything but small:
for the 200 m³ room of the example below at 21.4 °C and 54 % RH, the
ISO 9613-1 attenuation makes $4Vm$ about 0.9 m² at 1 kHz, 4.9 m² at 4 kHz and
7.2 m² at 5 kHz; against an empty-room absorption area of about 7.7 m² in
that top band. A few percent of humidity drift between the two runs therefore
moves $\alpha_\mathrm{s}$ by more than most of the effect being measured. When the
climate did drift, drop to `absorption_coefficient` and supply a separate
value per measurement as `m1`/`m2` (with `temperature1_c`/`temperature2_c`);
`measure_sound_absorption` assumes one climate. The per-band $m$ comes from
an ISO 9613-1 attenuation $\alpha$ in dB/m:
`environment.air_attenuation(freqs, temperature_c=21.4,
relative_humidity_percent=54.0, static_pressure_kpa=101.325)`, converted
with `materials.power_attenuation_from_alpha(alpha)`,
which is ISO 354's own $m = \alpha/(10 \lg e)$.

ISO 354 is a characterisation: it produces the $\alpha_\mathrm{s}$ spectrum, not a
single-number rating. The weighted coefficient $\alpha_\mathrm{w}$ is an ISO 11654
quantity; feed the measured $\alpha_\mathrm{s}$ to `weighted_absorption_from_third_octave`
in section 3 to obtain it.

```python
import numpy as np
from phonometry import materials

freqs = np.array([100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
                  1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000], float)
t_empty = np.array([9.0, 9.0, 8.8, 8.6, 8.4, 8.2, 8.0, 7.8, 7.5, 7.2,
                    6.9, 6.6, 6.2, 5.8, 5.4, 5.0, 4.6, 4.2])
t_specimen = np.array([8.4, 8.2, 7.7, 7.2, 6.5, 5.7, 4.9, 4.2, 3.6, 3.15,
                       2.85, 2.65, 2.55, 2.5, 2.55, 2.6, 2.7, 2.85])

meas = materials.measure_sound_absorption(
    t_empty, t_specimen, frequencies=freqs, volume=200.0, area=10.8, temperature_c=20.0
)
print(meas.alpha_s[7])   # alpha_s at 500 Hz: 0.328...
meas.plot()              # alpha_s versus one-third-octave frequency
```

![ISO 354 reverberation-room sound absorption: the alpha_s spectrum of a porous absorber sample over the one-third-octave bands from 100 Hz to 5000 Hz, rising from near zero at low frequency to a broad maximum around 0.69 near 1600 Hz and easing off above](https://docs.jmrp.io/phonometry/media/sound_absorption_measurement.svg)

*The Sabine inversion of the two decay times: the porous sample barely
changes the long low-frequency decays ($\alpha_\mathrm{s} \to 0$), bites hardest where
its thickness approaches a quarter wavelength, and eases off at high
frequency, a typical thin-porous-absorber signature (Cox & D'Antonio 3e,
Ch. 5).*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import materials

freqs = np.array([100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
                  1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000], float)
t_empty = np.array([9.0, 9.0, 8.8, 8.6, 8.4, 8.2, 8.0, 7.8, 7.5, 7.2,
                    6.9, 6.6, 6.2, 5.8, 5.4, 5.0, 4.6, 4.2])
t_specimen = np.array([8.4, 8.2, 7.7, 7.2, 6.5, 5.7, 4.9, 4.2, 3.6, 3.15,
                       2.85, 2.65, 2.55, 2.5, 2.55, 2.6, 2.7, 2.85])
meas = materials.measure_sound_absorption(
    t_empty, t_specimen, frequencies=freqs, volume=200.0, area=10.8, temperature_c=20.0
)

# One line: the alpha_s spectrum over the one-third-octave band axis.
meas.plot()
plt.show()

# By hand, from the result's fields:
fig, ax = plt.subplots()
ax.plot(np.arange(freqs.size), meas.alpha_s, "o-")
ax.set_xticks(np.arange(freqs.size))
ax.set_xticklabels([f"{f:g}" if f < 1000 else f"{f/1000:g}k" for f in freqs],
                   rotation=45)
ax.set_xlabel("Frequency [Hz]")
ax.set_ylabel(r"Sound absorption coefficient $\alpha_\mathrm{s}$")
plt.show()
```

### 1.1 How $T_1$ and $T_2$ are actually measured (Clause 7)

The two reverberation times are ordinary decay measurements (the machinery is
the one described under
[room acoustics](https://docs.jmrp.io/phonometry/buildings/rooms/room-acoustics/)), but ISO 354
constrains the geometry and the averaging much harder than a general room
survey does, because the whole result is the *difference* of two numbers that
are almost equal at low frequency.

**Where the transducers go (Clause 7.1).** Both the microphones and the sound
source are omnidirectional. Microphone positions are at least 1.5 m apart,
2 m from any sound source and 1 m from any room surface *and from the test
specimen*; source positions are at least 3 m apart. Decay curves measured at
different microphone positions shall not be combined in any way: they are
separate decays, averaged only as reverberation times.

**How many decays (Clause 7.1.4).** At least twelve spatially independent
decay curves: the number of microphone positions times the number of source
positions must reach 12, with a minimum of three microphone positions and two
source positions. Several sources may be driven simultaneously if their
radiated powers agree within 3 dB in every one-third-octave band, and that
buys a reduction to six curves.

**How the room is excited (Clause 7.2 or 7.3).** Two methods are allowed. The
*interrupted-noise* method drives a loudspeaker with broadband or band-limited
noise of continuous spectrum: with broadband noise and a real-time analyser
the resulting sound pressure levels must differ by less than 6 dB between
adjacent one-third-octave bands, and band-limited noise must be at least one
one-third octave wide. The excitation must run long enough to reach the steady
state (at least half the expected reverberation time) and start high enough
that the bottom of the evaluation range still clears the background by 10 dB.
Because a single interrupted decay is a statistical sample, averaging at one
microphone/source position is mandatory: **at least three** decays, and at
least ten if the repeatability is to match the other method. The *integrated
impulse response* method (a sweep or a maximum-length sequence deconvolved
into the impulse response) is deterministic and needs no averaging at all,
which is why it is the method to prefer when the instrumentation allows it.

**How each decay is read (Clause 7.4.1).** Per band: start 5 dB below the
initial level, evaluate over a 20 dB range, and keep the bottom of that range
at least 10 dB above the overall background noise: a $T_{20}$, extrapolated
to 60 dB. $T_1$ and $T_2$ are then the arithmetic mean over all the
measurements in that band, carried to at least two decimal places
(Clause 8.1.1).

**Then do it again.** The whole grid is repeated with the specimen installed
and *nothing else changed*: same positions, same excitation, same climate. Any
difference between the two runs other than the specimen ends up inside
$A_2 - A_1$ and is reported as absorption.

### 1.2 The specimen and its mounting (Clause 6.2 and Annex B)

**Geometry (Clause 6.2.1).** The test area is between 10 m² and 12 m²; above a
room volume of 200 m³ the *upper* limit is multiplied by $(V/200)^{2/3}$, and a
weakly absorbing specimen should use the upper limit. The specimen is
rectangular with a width-to-length ratio between 0.7 and 1, placed so that no
part is closer than 1 m to a room boundary and never closer than 0.75 m, with
its edges preferably *not* parallel to the nearest room edge (both rules
exist to keep the specimen out of the pressure maxima at the room boundaries).
A heavy specimen may instead stand vertically against a wall resting on the
floor, and then the 0.75 m clearance does not apply.

**The mounting is part of the result.** Annex B is normative and defines the
mounting catalogue a datasheet quotes:

| Type | What it is |
| :--- | :--- |
| A | Specimen laid or fixed directly against a room surface, normally the reverberation-room floor, with no air space |
| B | Glued to a gypsum board with adhesive dabs and 3 mm shims at the four corners, so a thin air space is retained |
| E-*xxx* | Mounted over a sealed air space in a fixture of at least 20 kg/m²; the suffix is the distance in millimetres from the **exposed face** of the specimen to the room surface behind it, tested at E-200, E-300 or E-400 |
| G-*xxx* | Hung parallel to a room surface (curtains, drapes, blinds); the suffix is again the face-to-surface distance, tested at G-100, other spacings in multiples of 50 mm |
| I | Sprayed or trowelled materials, applied to a substrate and then tested as a Type A with a frame |
| J | Unit absorbers (pads and baffles) in two or three parallel rows over 10 m² to 15 m² of floor, surrounded by a non-absorptive barrier |

The suffix is a cavity depth, and cavity depth moves the answer more than most
material choices do. Predicting the same 50 mm blanket
($\sigma = 20$ kPa·s/m²) with the
[multilayer models](https://docs.jmrp.io/phonometry/materials/absorbers/porous-absorbers/) gives
$\alpha_\mathrm{w} = 0.70(\text{H})$, class C, laid flat as a Type A, and
$\alpha_\mathrm{w} = 0.90$, class A, on a Type E-400 mounting. Two classes come from one
product because the 350 mm of air behind it moves the layer into the
particle-velocity maximum at 250 Hz (where the predicted coefficient goes from
0.37 to 0.86); the porous absorbers guide
[plays that move](https://docs.jmrp.io/phonometry/materials/absorbers/porous-absorbers/#spacing-the-layer-off-the-wall)
at normal incidence, the layer leaving the wall and the velocity it meets. A
quoted $\alpha_\mathrm{s}$ or $\alpha_\mathrm{w}$ without its mounting is
therefore not a material property but an installation result, which is why the
`mounting` field of the fiche below is not decoration.

**The perimeter edge (Annex B.2).** The specimen edges shall be sealed or
covered so that they do not absorb (unless the product is normally
installed with exposed edges, in which case they stay open and the area of the
edges is added into $S$). Either way the treatment goes in the report. Where a
reflective frame is used it must be solid rather than hollow, with no air
space between frame, specimen and room surface, at least 1.0 mm steel or
12.5 mm gypsum board or wood, tightly butted and sealed, its exposed face
flush with the face of the specimen. One consequence is easy to miss:
Clause 6.2.1.3 requires the **empty-room** measurement to be made *without*
the frame or the specimen's side walls (the barrier of a Type J mounting being
the exception), or the frame's own absorption never cancels out of
$A_2 - A_1$.

### 1.3 Is the room fit to measure in? (Clause 6.1 and Annex A)

Three checks decide whether a room may be used at all, and none of them is
performed by this library: `measure_sound_absorption` only raises an advisory
`AbsorptionWarning` on the volume and the specimen area.

1. **Volume and shape (Clauses 6.1.1, 6.1.2).** $V \ge 150$ m³, and at least
   200 m³ is strongly recommended for a new room; above roughly 500 m³ the
   high-frequency bands become inaccurate because air absorption dominates the
   decay. The shape must satisfy $l_\text{max} < 1.9\,V^{1/3}$, with
   $l_\text{max}$ the longest straight line inside the room (the major
   diagonal of a rectangular room), and no two room dimensions may stand in
   the ratio of small whole numbers (both conditions spread the low-frequency
   modes).
2. **Empty-room absorption (Clause 6.1.4).** $A_1$ shall not exceed the
   Table 1 ceiling, which is 6.5 m² from 100 Hz to 800 Hz for a 200 m³ room
   and rises through 7.0 m² at 1 kHz to 14.0 m² at 5 kHz; for another volume
   the whole table is scaled by $(V/200)^{2/3}$. The $A_1(f)$ curve must also
   be smooth, with no dip or peak differing by more than 15 % from the mean of
   the two adjacent one-third-octave bands. This is the single check that says
   the room itself is quiet enough acoustically to see a specimen at all: a
   leaky, lined or cluttered room spends its absorption budget on itself.
3. **Diffusivity (Annex A).** Diffusers are sheets of low absorption, about
   5 kg/m², individually 0.8 m² to 3 m² on one side, slightly curved,
   randomly oriented and spread through the room; rotating vanes are the
   alternative, and their rotation frequency must not stand in a
   small-whole-number ratio to the decay repetition frequency. The
   qualification procedure of A.2 is empirical: mount a homogeneous porous
   specimen 5 cm to 10 cm thick whose absorption exceeds 0.9 over 500 Hz to
   4000 Hz, measure it with no diffusers, then with about 5 m² of diffusers,
   then in further 5 m² steps, and plot the mean coefficient over 500 Hz to
   5000 Hz against diffuser area. The curve rises and then flattens; the
   optimum is where it stops rising. In a rectangular room that typically
   lands at 15 % to 25 % of the room's total surface area (counting both sides
   of each diffuser).

**What the report must carry (Clause 9).** The fiche below holds the specimen
description, $S$, the mounting, $V$, $c$, the temperature and humidity and the
$T_1$/$T_2$ and $A_1$/$A_2$ tables (with `verbose=True`), that is items (c),
(e) in part, (f) and (g). Four Clause 9 items have no `ReportMetadata` field
and must be appended by the laboratory: the shape of the room and its **total
surface area** $S_\mathrm{t}$, the number and size of the diffusers, the number of
microphone and source positions, and the treatment given to the specimen
edges. Results are reported with $A_\mathrm{T}$ rounded to 0.1 m² and $\alpha_\mathrm{s}$ to
0.01 (Clause 8.3).

### ISO 354 report (`.report()`)

`SoundAbsorptionMeasurement.report(path)` renders a one-page PDF fiche laid out
like an accredited reverberation-room absorption test report (ISO 354:2003): a
standard-basis line, a metadata header block, the one-third-octave $\alpha_\mathrm{s}$
table beside the $\alpha_\mathrm{s}$ curve (the result's own `.plot()`), a boxed
characterisation headline and a footer with the fixed disclaimer. ISO 354 has
no pass/fail verdict and no single-number rating, so the fiche carries neither.
Setting `verbose=True` adds the reverberation times $T_1$/$T_2$ and the
equivalent absorption areas $A_1$/$A_2$ to the table.

It uses the same `ReportMetadata` container and rendering engine as the other
fiches. The specimen area $S$, room volume $V$, speed of sound $c$, temperature
and humidity are taken from the measurement result (they drove the Sabine
inversion); the descriptive `ReportMetadata` fields that apply here are
`client`, `manufacturer`, `specimen`, `mounting`, `test_room`, `test_date`,
`static_pressure_kpa`, `measurement_standard`, `laboratory`, `operator`,
`report_id` and `notes`. The `requirement` field is ignored (ISO 354 has no
verdict). Rendering needs reportlab and, for the figure the fiche embeds,
matplotlib (`pip install "phonometry[report,plot]"`); only `engine="reportlab"`
is supported. The fiche renders in English by default; pass `language="es"` for
a Spanish fiche (translated fixed strings and a comma decimal separator).

```python
from phonometry import materials, ReportMetadata

meas = materials.measure_sound_absorption(
    t_empty, t_specimen, frequencies=freqs, volume=200.0, area=10.8,
    temperature_c=20.0, relative_humidity_percent=54.0,
)
meas.report(
    "alpha_s_fiche.pdf",
    metadata=ReportMetadata(
        specimen="50 mm porous absorber over a 100 mm air gap",
        mounting="Type A (against a rigid wall)",
        measurement_standard="ISO 354",
        test_room="Reverberation room R1",
        laboratory="Phonometry Reference Laboratory",
    ),
)                                  # one-third-octave alpha_s, 100 Hz to 5000 Hz
```

**Report:** [ISO 354 absorption example report (PDF)](https://docs.jmrp.io/phonometry/media/iso354_absorption_example.pdf): One-page reverberation-room sound absorption fiche: a metadata header (client, specimen, sample area S, room volume V, speed of sound c, mounting, reverberation-room temperature, humidity and pressure), the one-third-octave alpha_s table grouped by octave beside the alpha_s curve, and the boxed characterisation headline over the tested one-third-octave range.

Reverberation-room absorption fiche (SoundAbsorptionMeasurement.report), the alpha_s spectrum.

## 2. The same inversion on bare arrays: `absorption_area` and `absorption_coefficient`

Section 1 returns a whole `SoundAbsorptionMeasurement`: it carries the room and
specimen metadata, plots itself and renders the ISO 354 fiche. When all that is
wanted is the arithmetic (inside a loop, a fit, a spreadsheet import, or when
the quantity of interest is the room's own equivalent absorption area rather
than a specimen coefficient), the same Eqs. (5) to (9) are exposed as two plain
array functions. The equivalent absorption area $A$ is also what drives $R'$,
$L'_n$, the ISO 3744 $K_2$ environmental correction and the ISO 3741 absorption
term, and `absorption_area` is the entry point those calculations use.

```python
import numpy as np
from phonometry import materials

# Third-octave reverberation times of a 200 m^3 room, empty (T1) and with a
# 10.8 m^2 absorber sample installed (T2).
t1 = np.array([5.0, 4.0, 3.0])
t2 = np.array([3.0, 2.5, 2.0])

a_empty = materials.absorption_area(t1, volume=200.0, temperature_c=20.0)
print(np.round(a_empty, 2))                    # [ 6.45  8.06 10.75] m^2

alpha = materials.absorption_coefficient(t1, t2, volume=200.0, sample_area=10.8,
                               temperature1_c=20.0)
print(np.round(alpha, 3))                      # [0.398 0.448 0.498]
```

$T_1$ and $T_2$ are exactly the reverberation times [`room_parameters`](https://docs.jmrp.io/phonometry/buildings/rooms/room-acoustics/) returns, so
an ISO 3382-2 decay measurement of the empty and treated room flows straight
into `absorption_coefficient`.

The result object of section 1 keeps every intermediate of that inversion:
`t_empty`, `t_specimen`, `absorption_area_empty` and
`absorption_area_with_specimen`. They are worth looking at, because they
show where the method is strong and where it is running out of signal:

![Two stacked panels over the one-third-octave axis from 100 Hz to 5 kHz. The upper panel plots the empty-room reverberation time T1 and the with-specimen time T2, which nearly coincide at 100 Hz and separate widely above 500 Hz. The lower panel plots the equivalent absorption areas A1 and A2 with the difference A2 minus A1 filled between them, and a right-hand axis reading the resulting alpha_s](https://docs.jmrp.io/phonometry/media/sound_absorption_inversion.svg)

*The whole ISO 354 inversion of the section 1 example, drawn: the two decay
times (top) and the two Sabine areas they invert to (bottom), with the filled
difference $A_2 - A_1$ divided by $S = 10.8$ m² giving the $\alpha_\mathrm{s}$ on the
right-hand axis. At 100 Hz the two decays differ by 0.6 s out of 9 s and the
filled band is barely visible, which is exactly why the uncertainty of
section 4 is worst there. By 1.6 kHz the specimen has more than halved the
decay and the difference is unmistakable.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt

# `meas` is the SoundAbsorptionMeasurement of section 1; every quantity the
# figure draws is a field of it.
fig, (ax_t, ax_a) = plt.subplots(2, 1, sharex=True, figsize=(10, 7))
band = np.arange(freqs.size)
ax_t.plot(band, meas.t_empty, "o-", label="T1 (empty room)")
ax_t.plot(band, meas.t_specimen, "s-", label="T2 (specimen installed)")
ax_t.set_ylabel("Reverberation time [s]")
ax_t.legend()

a1 = meas.absorption_area_empty
a2 = meas.absorption_area_with_specimen
ax_a.plot(band, a1, "o-", label="A1 (empty room)")
ax_a.plot(band, a2, "s-", label="A2 (with specimen)")
ax_a.fill_between(band, a1, a2, alpha=0.25, label="A2 - A1")
ax_a.set_ylabel("Equivalent absorption area [m$^2$]")
ax_a.set_xticks(band)
ax_a.set_xticklabels([f"{f:g}" if f < 1000 else f"{f/1000:g}k" for f in freqs],
                     rotation=45)
ax_a.set_xlabel("Frequency [Hz]")
ax_a.legend()
plt.show()

print(np.round((a2 - a1) / 10.8 - meas.alpha_s, 12).max())   # 0.0: same alpha_s
```

Each of those two numbers is read off a decay, and the clip below shows how
one is read: the squared impulse response is integrated backwards from the
tail, the Schroeder curve emerges, and the T20 and T30 regressions are fitted
to a straight portion of it. That is the operation behind $T_1$, and again
behind $T_2$ (the clip shows a *single* room, not the pair, so it answers
"where does one $T$ come from" and not "what does subtracting two of them
cost"). The second question is the one that governs this measurement, and
section 4 puts a number on it: because $\alpha_\mathrm{s}$ is a difference of two
reciprocal decay times, its uncertainty is worst exactly where the two decays
are most alike, at the low-frequency end.

**Video:** [Schroeder backward integration of the squared impulse response](https://docs.jmrp.io/phonometry/media/anim_schroeder.webm): The tail energy of the squared impulse response fills from the end while the backward integral advances toward t = 0, and the Schroeder decay curve emerges on a companion axis, ending with the T20 and T30 regression lines.

A room volume below the 150 m³ minimum or a
sample area outside 10–12 m² raises an advisory `AbsorptionWarning`; the result
still returns.

### `absorption_area()` / `absorption_coefficient()` parameters

| Parameter | Type | Units | Range / default | Notes |
| :--- | :--- | :--- | :--- | :--- |
| `t60` / `t1`, `t2` | 1D array | s | > 0 | Reverberation time(s); `t1` empty, `t2` with specimen |
| `volume` | float | m³ | > 0 | Room volume $V$ (advisory below 150 m³) |
| `sample_area` | float | m² | > 0 | Area $S$ the specimen covers (coefficient only) |
| `temperature_c` / `temperature1_c`, `temperature2_c` | float | °C | default `20.0`, 15–30 | Sets $c$ via Eq. (6); `temperature2_c` defaults to `temperature1_c` |
| `speed_of_sound` (`…1`, `…2`) | float, optional | m/s | > 0 | Overrides the temperature-derived $c$ |
| `m` (`m1`, `m2`) | float or 1D array | 1/m | ≥ 0, default `0` | Air power attenuation coefficient |

`absorption_area()` returns the equivalent absorption area $A$ (m²) with the
shape of `t60`; `absorption_coefficient()` returns $\alpha_\mathrm{s}$;
`power_attenuation_from_alpha(alpha)` converts an ISO 9613-1 $\alpha$ (dB/m) to $m$.

## 3. Weighted rating and absorption class (ISO 11654)

The measurement of section 1 delivers the $\alpha_\mathrm{s}$ spectrum in
one-third-octave bands. ISO 11654:1997 turns that spectrum into a
single-number rating comparable across products.

![ISO 11654 rating flow: measured alpha_s becomes practical alpha_p per octave band, the reference curve is shifted to best fit, alpha_w is read at 500 Hz with shape indicators, giving the absorption class A to E](https://docs.jmrp.io/phonometry/media/diagram_iso11654.svg)

**Practical absorption coefficient (Clause 4.1).** The one-third-octave data are
first grouped into octave bands, each the arithmetic mean of its three thirds:

$$
\alpha_{\mathrm{p},i} = \tfrac{1}{3}\big(\alpha_{i1} + \alpha_{i2} + \alpha_{i3}\big),
$$

evaluated to the second decimal and then rounded in steps of $0.05$ (the
Clause 4.1 NOTE fixes the rounding, e.g. $0.92 \to 0.90$); rounded means above
$1.00$ are set to $1.00$. The five rating bands are 250, 500, 1000, 2000 and
4000 Hz.

**Weighted absorption (Clause 4.2).** A fixed reference curve
$\{250{:}\,0.80,\ 500{:}\,1.00,\ 1000{:}\,1.00,\ 2000{:}\,1.00,\ 4000{:}\,0.90\}$
is shifted downwards, towards the measured $\alpha_\mathrm{p}$, in steps of $0.05$ until
the sum of the **unfavourable** deviations (taken only where the measurement
lies below the shifted curve, with magnitude $(\text{curve} - \text{measured})$)
is no more than $0.10$. The weighted coefficient $\alpha_\mathrm{w}$ is the shifted-curve
value read at 500 Hz.

**Shape indicators (Clause 4.3).** When a practical coefficient exceeds the
shifted curve by $0.25$ or more, a shape indicator is appended: `L` at 250 Hz,
`M` at 500 or 1000 Hz, `H` at 2000 or 4000 Hz (e.g. `0.60(M)`).

**Absorption class (Table B.1).** Finally $\alpha_\mathrm{w}$ maps to a class: A
(0.90–1.00), B (0.80–0.85), C (0.60–0.75), D (0.30–0.55), E (0.15–0.25), or "not
classified" (0.00–0.10). Because $\alpha_\mathrm{w}$ is always a multiple of $0.05$ these
ranges partition the grid exactly.

**What the rating cannot say.** ISO 11654 scopes itself in Clause 1.2, and the
four limits it states there are exactly the cases a practitioner meets. The
reference curve starts at the 250 Hz octave, so everything the specimen does
at 100 Hz to 200 Hz is outside the rating by construction and the standard
says the rating "is not appropriate below this frequency"; a bass treatment
and a mid-frequency panel can share an $\alpha_\mathrm{w}$ while differing by half a
coefficient at 125 Hz. The rating is likewise "not applicable unless the
applications cover the whole frequency range of the reference curve". If only
part of the range matters, the standard sends the reader back to the spectrum,
and points at the shape indicators as the hint that a modest $\alpha_\mathrm{w}$ with
an `(L)` may be the better product for a low-frequency problem. It is scoped
to *routine* applications (normal offices, corridors, classrooms, hospitals)
and declares itself inappropriate for "qualified environments requiring
careful acoustical design by expertise", where only the full spectrum will do.
And it is "often not suitable for application to single items, such as chairs,
baffles, etc." (whose absorption is an equivalent area per object, not a
coefficient), nor is it applicable to road barriers and road surfaces, which
have [EN 1793-1](#4-sound-absorption-measurement-uncertainty-iso-12999-2) and
[ISO 13472](https://docs.jmrp.io/phonometry/materials/surfaces/road-absorption/) of their own.
This is why the fiche always prints the whole spectrum beside the single
number.

![ISO 11654 weighted sound absorption rating: the practical absorption spectrum plotted against the shifted reference curve over 250 Hz to 4000 Hz, with the unfavourable deviation at 250 Hz shaded and the weighted coefficient alpha_w read at 500 Hz](https://docs.jmrp.io/phonometry/media/absorption_rating.svg)

*The Annex A.2 worked example: the reference curve is shifted down by 0.40 until
the unfavourable deviations sum to 0.05 ($\le 0.10$), giving $\alpha_\mathrm{w} = 0.60$;
the 500 Hz peak overshoots the shifted curve by $\ge 0.25$, adding the `M`
indicator, so the rating is $0.60(\text{M})$, class C.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
from phonometry import materials

# ISO 11654 Annex A.2 practical coefficients at 250/500/1000/2000/4000 Hz
result = materials.weighted_absorption([0.35, 1.00, 0.65, 0.60, 0.55])
result.plot()   # practical curve vs shifted reference, deviations shaded
plt.show()
```

```python
from phonometry import materials

# ISO 11654 Annex A.2 practical coefficients at 250/500/1000/2000/4000 Hz
alpha_p = [0.35, 1.00, 0.65, 0.60, 0.55]

result = materials.weighted_absorption(alpha_p)
print(result.rating_label)          # 0.60(M)
print(result.alpha_w)               # 0.6
print(result.absorption_class)      # C
print(round(result.unfavorable_sum, 2))  # 0.05
result.plot()   # the figure above: practical curve vs shifted reference

# A bare alpha_w also maps straight to its class (Table B.1)
print(materials.absorption_class(0.85))       # B
```

`weighted_absorption` accepts the five octave-band $\alpha_\mathrm{p}$ values (as a
sequence or a `{frequency: value}` mapping); pass the fifteen one-third-octave
$\alpha_\mathrm{s}$ values to `practical_absorption_coefficient` first if you are starting
from raw ISO 354 data. To keep the one-third-octave $\alpha_\mathrm{s}$ on the result (so
the fiche can print the full table every accredited ISO 354 certificate carries),
rate it in one step with `weighted_absorption_from_third_octave(alpha_s)`, which
forms $\alpha_\mathrm{p}$, rates it and retains the input $\alpha_\mathrm{s}$ and its band centres
(`third_octave_alpha_s`, `third_octave_bands`). The result carries the shifted
reference curve and the per-band deviations, and its `.plot()` renders the figure
above.

```python
from phonometry import materials

# Fifteen one-third-octave alpha_s (200 Hz to 5000 Hz), as an ISO 354 report gives
alpha_s = [0.30, 0.35, 0.40, 1.00, 1.00, 1.00, 0.62, 0.66, 0.67,
           0.58, 0.60, 0.62, 0.53, 0.55, 0.57]
result = materials.weighted_absorption_from_third_octave(alpha_s)
print(result.rating_label)          # 0.60(M)
print(result.third_octave_alpha_s)  # the input alpha_s, retained for the fiche
```

**Is that a good number?** Absorption tracks thickness against wavelength, so
every halving of the useful frequency costs a doubling of thickness or of
cavity depth, and the ladder is short. Predicting a mineral-wool-class
material ($\sigma = 20$ kPa·s/m²) hard against a wall with the
[multilayer models](https://docs.jmrp.io/phonometry/materials/absorbers/porous-absorbers/) gives a
random-incidence coefficient at 500 Hz of about 0.32 for a 25 mm blanket, 0.68
for 50 mm and 0.89 for 100 mm; at 250 Hz the same three give 0.14, 0.37 and
0.74. Spacing the 50 mm layer off the wall on a 100 mm cavity lifts its 250 Hz
value from 0.37 to 0.68: the cavity buys roughly the octave that doubling the
material would have bought. A painted or sealed hard surface sits at a few
hundredths across the whole range. The practical reading: class A is nearly
always a thick or a spaced construction rather than a clever surface, and a
thin sample that reports a mid-frequency $\alpha_\mathrm{s}$ above about 1.1, or a
rising low-frequency tail, is showing an edge effect or a mounting leak rather
than a good material. Measured ISO 354 values also run above these predicted
ones, by roughly 0.1 to 0.2 in the mid bands, for the finite-sample reason set
out in the closing section.

### ISO 11654 report (`.report()`)

`AbsorptionRatingResult.report(path)` renders a one-page PDF fiche laid out like
an accredited absorption test report (an ISO 354 reverberation-room measurement
rated per ISO 11654): a standard-basis line, an optional metadata header block,
the octave-band $\alpha_\mathrm{p}$ table beside the practical-versus-shifted-reference
plot (the result's own `.plot()`), the boxed $\alpha_\mathrm{w}$ single number with its
absorption class and applied shift, an optional verdict row and a footer with
the fixed disclaimer. When the rating was built with
`weighted_absorption_from_third_octave`, the left table becomes the full ISO 354
one-third-octave $\alpha_\mathrm{s}$ table with the octave $\alpha_\mathrm{p}$ on the matching
rows, exactly as accredited certificates print it. It uses the same
`ReportMetadata` container and rendering engine as the
[ISO 717 insulation fiche](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-ratings/#iso-717-report-report);
passing `metadata=None` produces a lightweight prediction fiche, and a supplied
`requirement` is read as the minimum $\alpha_\mathrm{w}$ for the PASS/FAIL verdict.
Setting `verbose=True` swaps the two-column table for the ISO 11654 evaluation
columns (practical coefficient, shifted reference, unfavourable deviation).
Rendering needs reportlab and, for the figure the fiche embeds, matplotlib (`pip
install "phonometry[report,plot]"`); only `engine="reportlab"` is supported. The
fiche renders in English by default; pass `language="es"` for a Spanish fiche
(translated fixed strings and a comma decimal separator), e.g.
`result.report("alpha_w_fiche_es.pdf", language="es")`.

```python
from phonometry import materials, ReportMetadata

# Rate from the fifteen one-third-octave alpha_s so the fiche prints the full
# ISO 354 table; materials.weighted_absorption([...]) also works from alpha_p.
alpha_s = [0.30, 0.35, 0.40, 1.00, 1.00, 1.00, 0.62, 0.66, 0.67,
           0.58, 0.60, 0.62, 0.53, 0.55, 0.57]
result = materials.weighted_absorption_from_third_octave(alpha_s)
result.report(
    "alpha_w_fiche.pdf",
    metadata=ReportMetadata(
        specimen="50 mm porous absorber over a 100 mm air gap",
        area=10.8, mounting="Type A (against a rigid wall)",
        measurement_standard="ISO 354",
        temperature_c=21.4, relative_humidity_percent=54.0,
        laboratory="Phonometry Reference Laboratory",
        requirement=0.55,          # adds the PASS/FAIL verdict row
    ),
)                                  # alpha_w (shape) + absorption class
```

The example fiche is regenerated with `make reports` and kept rendered in the
repository; click the preview to open the PDF.

**Report:** [ISO 11654 absorption example report (PDF)](https://docs.jmrp.io/phonometry/media/iso11654_absorption_example.pdf): One-page sound absorption fiche: a metadata header (client, specimen, sample area, mounting, reverberation-room temperature, humidity and pressure), the full one-third-octave alpha_s table with the octave alpha_p on the matching rows beside the practical-versus-shifted-reference plot, the boxed alpha_w = 0.60 (M) single-number result with absorption class C and the applied shift, and a PASS verdict against the 0.55 requirement.

Weighted absorption fiche (AbsorptionRatingResult.report), alpha_w with its class.

## 4. Sound-absorption measurement uncertainty (ISO 12999-2)

A rated absorption coefficient means little without its uncertainty. ISO
12999-2:2020 gives the standard uncertainty $u$ of the quantities produced by a
reverberation-room measurement (ISO 354) and its ratings (ISO 11654, EN 1793-1),
estimated from inter-laboratory tests to ISO 5725. It is the sound-absorption
companion of the sound-insulation uncertainty of ISO 12999-1
([Field Insulation Measurement (ISO 16283)](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-field/)).

**One-third-octave bands (Clause 5).** For the sound-absorption coefficient the
reproducibility standard deviation is $\sigma_\mathrm{R} = m_\mathrm{R}\,\alpha_\mathrm{s} + n_\mathrm{R}$
(Formula (1)), and for the equivalent absorption area
$\sigma_\mathrm{R} = m_\mathrm{R}\,A_\mathrm{T} + n_\mathrm{R}\,S$ with $S = 10\ \text{m}^2$ (Formula (2)), where
$m_\mathrm{R}$ and $n_\mathrm{R}$ are the frequency-dependent regression constants of Table 1
(63–5000 Hz): nothing to do with the air power attenuation coefficient $m$ of
section 1, which shares the standards' letter and not its meaning. The
repeatability value is $\sigma_\mathrm{r} = 0.6\,\sigma_\mathrm{R}$ (Formula (3)). Note that the
$n_\mathrm{R}$ term of Formula (2) is multiplied by a *fixed* reference area of 10 m²
rather than by the specimen's own area, so a small specimen's $A_\mathrm{T}$ is
proportionally far less certain than a large one's (which is one more reason
ISO 354 pins the test area between 10 m² and 12 m²).

**Practical coefficient (Clause 6).** For the ISO 11654 practical coefficient
$\sigma_\mathrm{R} = m_\mathrm{R}\,\alpha_\mathrm{p} + n_\mathrm{R}$ in octave bands with the constants of Table 2
(250–4000 Hz); again $\sigma_\mathrm{r} = 0.6\,\sigma_\mathrm{R}$. Table 2 covers those five
octaves only, so the 125 Hz octave has no tabulated uncertainty and
`practical_coefficient_uncertainty` rejects it rather than returning a blank.

**Single numbers (Clause 7).** The weighted coefficient $\alpha_\mathrm{w}$ has a constant
standard uncertainty ($\sigma_\mathrm{R} = 0.035$, $\sigma_\mathrm{r} = 0.020$); the EN 1793-1
single-number rating $DL_{\alpha,\text{NRD}}$ scales with the value
($\sigma_\mathrm{R} = 0.10\,DL_\alpha$, $\sigma_\mathrm{r} = 0.02\,DL_\alpha$).

**Reporting (Clause 8).** The expanded uncertainty is $U = k\,u$ (Formula (10))
with the Table 3 coverage factor $k$ ($k = 2.0$ at 95 %, Gaussian; read another
coverage probability off the same table with `absorption_coverage_factor`, which returns
2.6 at 99 %). The reported $U$ is rounded to two decimals for absorption
coefficients and one decimal for the equivalent area and
$DL_{\alpha,\text{NRD}}$.

![ISO 12999-2 sound absorption coefficient uncertainty: the measured alpha_s spectrum over one-third-octave bands from 63 Hz to 5000 Hz with a shaded plus-or-minus U band at coverage factor k = 2, reproducing the standard's worked Table 4 example](https://docs.jmrp.io/phonometry/media/absorption_uncertainty.svg)

*The Table 4 worked example: the measured $\alpha_\mathrm{s}$ spectrum with its
$\pm U$ ribbon at $k = 2$ (95 %), where $\sigma_\mathrm{R} = m_\mathrm{R}\,\alpha_\mathrm{s} + n_\mathrm{R}$ takes
$m_\mathrm{R}$ and $n_\mathrm{R}$ from Table 1. The ribbon is a shallow U: $\pm 0.33$ in the
63 Hz band, tightening to $\pm 0.08$ from 250 Hz to 2 kHz and opening again to
$\pm 0.16$ at 5 kHz. The width is set almost entirely by the band, not by the
absorber: the low end is the modal field of the room, the high end is the air
absorption the two decays must be corrected for. The plotted $U$ is the
reported one, rounded to two decimals as Clause 8 requires.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
from phonometry import materials

# ISO 12999-2 Table 4 worked example: alpha_s per one-third-octave band.
freqs = [63, 80, 100, 125, 160, 200, 250, 315, 400, 500,
         630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000]
alpha_s = [0.33, 0.35, 0.39, 0.38, 0.37, 0.36, 0.36, 0.36, 0.43, 0.49,
           0.58, 0.63, 0.68, 0.71, 0.73, 0.75, 0.77, 0.79, 0.81, 0.81]
result = materials.sound_absorption_coefficient_uncertainty(alpha_s, frequencies=freqs, coverage=0.95)
result.plot()   # alpha_s with the +/-U (k = 2) reproducibility ribbon
plt.show()
```

```python
from phonometry import materials

# Reproducibility uncertainty of alpha_s at 1000 Hz (Table 1: m=0.040, n=0.015).
r = materials.sound_absorption_coefficient_uncertainty([0.68], frequencies=[1000], coverage=0.95)
print(round(float(r.standard_uncertainty[0]), 4))            # 0.0422 (sigma_R)
print(float(r.reported_expanded_uncertainty[0]))             # 0.08  (U, k=2)
r.plot()   # the figure above: alpha_s with its +/-U (k = 2) ribbon

# Same band, same value, but a repeat on my own bench rather than another
# laboratory: sigma_r = 0.6 sigma_R (Formula (3)).
rr = materials.sound_absorption_coefficient_uncertainty(
    [0.68], frequencies=[1000], condition="repeatability"
)
print(round(float(rr.standard_uncertainty[0]), 5))           # 0.02532 = 0.6 x 0.0422

# The other two quantities this page produces, Formula (2) and Clause 6.
at = materials.equivalent_area_uncertainty([12.4], frequencies=[1000], coverage=0.95)
print(float(at.reported_expanded_uncertainty[0]))            # 1.3 m^2 on A_T = 12.4 m^2
ap = materials.practical_coefficient_uncertainty(
    [0.35, 1.00, 0.65, 0.60, 0.55], frequencies=[250, 500, 1000, 2000, 4000]
)
print(list(ap.reported_expanded_uncertainty))                # [0.07, 0.08, 0.08, 0.08, 0.1]

# Single-number ratings (Clause 7 worked examples).
print(float(materials.weighted_coefficient_uncertainty(0.70).reported_expanded_uncertainty[0]))  # 0.07
print(float(materials.single_number_rating_uncertainty(8.1).reported_expanded_uncertainty[0]))   # 1.6
```

**What those numbers mean.** An expanded uncertainty of 0.08 on a
one-third-octave $\alpha_\mathrm{s}$ is a statement about *two* laboratories: measuring
the same product, both correctly, they may legitimately report 0.64 and 0.72,
so a specification written to two decimals is not testable and a datasheet
value that misses your own measurement by less than the combined $U$ is
agreement, not a discrepancy. Within one laboratory the repeatability figure
applies instead: 0.6 of the reproducibility value, a spread about 40 %
narrower. So a repeat on your own bench that falls outside the narrower band
points at the specimen, the mounting or the room, not at the method. The
single numbers are worse than they look: $U(\alpha_\mathrm{w}) = 0.07$ exceeds the 0.05
step $\alpha_\mathrm{w}$ is quoted on, so a product measured at 0.85 (class B) cannot be
told apart from one at 0.90 (class A) by a single test. A tender that hinges on
a class letter is a tender decided by measurement noise; ask for the spectrum
and the uncertainty instead, and quote $U$ beside $\alpha_\mathrm{w}$ in the fiche.

## Tube or reverberation room?

The tube and the reverberation room both deliver a number called the
"absorption coefficient", and the two are routinely confused. They are
different physical quantities, measured under different sound fields, and they
do not match, sometimes not even closely.

The [tube](https://docs.jmrp.io/phonometry/materials/absorbers/impedance-tube/) measures a **normal-incidence** coefficient: one plane wave, one
angle, a specimen a few centimetres across, and a complex reflection factor
that keeps magnitude and phase. ISO 354 measures the **random-incidence**
coefficient $\alpha_\mathrm{s}$: a diffuse field striking a sample of 10 m² to 12 m²
from every direction at once, recovered from the change in the room's decay
time through Sabine's formula, an energy average with no phase left in it.
Because the diffuse field finds more ways into an absorber than the single
normal-incidence wave (oblique waves travel a longer path inside the layer),
$\alpha_\mathrm{s}$ usually comes out higher. For a locally reacting surface the two
are linked by Paris' angular average, which defines the statistical
absorption coefficient

$$
\alpha_\mathrm{st} = \int_0^{\pi/2} \alpha(\theta)\,\sin 2\theta\,\mathrm{d}\theta,
$$

an integral that weights the oblique angles most heavily. It needs the
angle-dependent $\alpha(\theta)$, not the normal-incidence coefficient itself.
But for a **locally reacting** surface $\alpha(\theta)$ follows from the
normalised surface impedance alone, so the integral has a closed form and a
tube result converts in one line:
`materials.statistical_absorption(result.normalized_impedance)`, documented
with the
[multilayer models](https://docs.jmrp.io/phonometry/materials/absorbers/porous-absorbers/#4-oblique-and-random-incidence).
What that cannot do is cover a **bulk-reacting** layer, where the oblique
behaviour depends on refraction inside the material and the integral has to be
evaluated angle by angle from a model: `diffuse_field_absorption`, on the same
page.

The size of the gap is worth seeing, because "usually higher" is not a useful
design statement:

![Absorption coefficient of a 50 mm hard-backed porous layer against frequency from 125 Hz to 4 kHz: the random-incidence Paris average lies above the normal-incidence curve, with the two converging as the layer becomes thick against the wavelength](https://docs.jmrp.io/phonometry/media/diffuse_field_absorption.svg)

*What the tube reads and what the room reads, for the same 50 mm hard-backed
porous layer ($\sigma = 20$ kPa·s/m², Miki): the tube measures
$\alpha(0°)$, the dashed curve, while the room measures the Paris average over
all angles, the solid one. The gap is widest where the layer is thin against
the wavelength: precisely the low-frequency region where a normal-incidence
number substituted into a Sabine or EN 12354-6 budget would underpredict the
installed absorption, and closes as the layer becomes electrically thick. It
is a model comparison on an infinite layer, so it is a lower bound on the real
difference: a finite ISO 354 specimen adds the edge effect on top.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt

# A 50 mm porous layer on a rigid backing, predicted both ways.
f = np.geomspace(125.0, 4000.0, 200)
layers = [materials.PorousLayer(thickness_m=0.05, medium=materials.miki(f, 20000.0))]
normal = materials.layered_absorber(f, layers)
diffuse = materials.diffuse_field_absorption(f, layers)
ax = diffuse.plot()
ax.plot(f, normal.absorption, ls="--", label="Normal incidence")
ax.legend()
plt.show()
```

**Why ISO 354 values exceed 1.** A ratio of absorbed to incident energy cannot
exceed one, yet reverberation-room reports of $\alpha_\mathrm{s} = 1.05$ to $1.20$ for
thick porous absorbers are routine and correct by the method. Sabine's formula
converts the decay-time change into an equivalent absorption area $A$, and
$\alpha_\mathrm{s} = A/S$ divides by the *geometric* sample area $S$. Diffraction at
the sample edges lets the specimen drain energy from a sound field wider than
its footprint (the edge effect), so the equivalent area can exceed the
geometric one. Such values are not errors, but they are not portable either:
they depend on the sample size and perimeter, which is precisely why ISO 354
fixes both. The ISO 11654 rating simply truncates: practical coefficients
above $1.00$ are set to $1.00$ (section 3). Prediction inputs get no such
silent clipping in this library: each
[reverberation-time estimator](https://docs.jmrp.io/phonometry/buildings/rooms/reverberation-prediction/)
enforces its own mathematical domain, so Sabine and Eyring accept ISO 354
values at or above one as supplied (Eyring as long as the mean absorption
stays below one), while Millington-Sette rejects them (its per-surface
logarithm diverges at one) and any adjustment below one is left to the
caller. The equivalent-absorption-area budget of
[EN 12354-6](https://docs.jmrp.io/phonometry/buildings/rooms/enclosed-space-absorption/) likewise accepts
the coefficients as supplied.

**Which to use.** They answer different questions. The reverberation-room
value is the one that feeds diffuse-field prediction: Sabine reverberation
estimates, the equivalent absorption areas of
[EN 12354-6](https://docs.jmrp.io/phonometry/buildings/rooms/enclosed-space-absorption/) and the $\alpha_\mathrm{w}$
rating and class, all of which expect random incidence over a mounted, finite
sample (ISO 354's Annex B mounting types exist because the mounting is part of
the result). The tube value is the laboratory and development tool: it needs
only a few square centimetres of material, resolves magnitude *and* phase, and
its surface impedance pins down the parameters of porous-material models in
the Allard and Atalla tradition, with the
[airflow resistivity](https://docs.jmrp.io/phonometry/materials/absorbers/airflow-resistance/) as the first
input; the fitted model then predicts the layer at any angle,
thickness or backing. What the tube number is *not* is a drop-in substitute
for $\alpha_\mathrm{s}$: feeding normal-incidence coefficients into a Sabine or
EN 12354-6 budget systematically underpredicts the installed absorption.

## What this guide covers

- **Covered.** The ISO 354:2003 Sabine inversion (Eqs. (5)-(9)) in
  `measure_sound_absorption`, and the Clause 4/8.1 conversion of an
  already-measured $T_1$/$T_2$ pair in `absorption_area` and
  `absorption_coefficient` (with `power_attenuation_from_alpha` for the air term). ISO
  11654:1997's weighted absorption rating: the practical coefficient of Clause
  4.1, the reference-curve shift of Clause 4.2, the shape indicators of Clause
  4.3, and the Table B.1 absorption class, built by `weighted_absorption` and
  `weighted_absorption_from_third_octave`. ISO 12999-2:2020's
  measurement-uncertainty formulae (Clauses 5-8), one function per quantity:
  `sound_absorption_coefficient_uncertainty` (Formula (1)),
  `equivalent_area_uncertainty` (Formula (2)),
  `practical_coefficient_uncertainty` (Clause 6),
  `weighted_coefficient_uncertainty` and `single_number_rating_uncertainty`
  (Clause 7), each taking `condition="reproducibility"` or `"repeatability"` for
  Formula (3), with the Table 3 coverage factor in `absorption_coverage_factor`.

- **Not covered.** Nothing on *this* page consumes a measured surface impedance: the conversion
  from a tube result to the statistical coefficient $\alpha_\mathrm{st}$ lives with the
  prediction models (`statistical_absorption` for a locally reacting surface,
  `diffuse_field_absorption` for a bulk-reacting one), and neither is a
  substitute for an ISO 354 measurement, because neither reproduces the edge
  effect. The room and specimen requirements of Clause 6 and Annex A are
  *described* in sections 1.2 and 1.3 but not *checked*: nothing here verifies
  the shape rule, the Table 1 ceiling on $A_1$, the diffusivity qualification or
  the microphone and source counts, and `absorption_area` /
  `absorption_coefficient` only convert an already-measured $T_1$/$T_2$ pair and
  raise an advisory warning when the room volume or sample area falls outside
  the Clause 6 limits. Neither is the decay measurement itself in scope; the
  interrupted-noise and integrated-impulse-response methods of Clause 7 belong
  to [room acoustics](https://docs.jmrp.io/phonometry/buildings/rooms/room-acoustics/). ISO
  12999-2's uncertainty formula for the EN 1793-1 single-number rating
  $DL_{\alpha,\text{NRD}}$ is implemented, but EN 1793-1's own in-situ
  measurement method (road-traffic noise-reducing devices) is not.

## See also

- [Impedance Tube](https://docs.jmrp.io/phonometry/materials/absorbers/impedance-tube/): the normal-incidence
  absorption, surface impedance and transmission loss of small samples, and
  why its coefficient differs from $\alpha_\mathrm{s}$.
- [Airflow Resistance](https://docs.jmrp.io/phonometry/materials/absorbers/airflow-resistance/): the ISO 9053
  flow resistivity that anchors the porous-material models behind most
  absorbers.
- [Porous and Multilayer Absorbers](https://docs.jmrp.io/phonometry/materials/absorbers/porous-absorbers/):
  predicting the absorption of a construction before it is built.
- [Room Acoustics](https://docs.jmrp.io/phonometry/buildings/rooms/room-acoustics/): the ISO 3382 decay
  measurements that supply the reverberation times $T_1$ and $T_2$.
- [Reverberation-time prediction](https://docs.jmrp.io/phonometry/buildings/rooms/reverberation-prediction/):
  the Sabine, Eyring and Millington-Sette estimators that consume $\alpha_\mathrm{s}$.
- [Equivalent absorption area of furnished rooms](https://docs.jmrp.io/phonometry/buildings/rooms/enclosed-space-absorption/):
  the EN 12354-6 absorption budget these coefficients feed.
- [Field Insulation Measurement (ISO 16283)](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-field/):
  the sound-insulation companion uncertainty standard, ISO 12999-1.
- API reference: [`materials.absorbers.sound_absorption`](https://docs.jmrp.io/phonometry/reference/api/materials/sound-absorption/), [`materials.absorbers.rating`](https://docs.jmrp.io/phonometry/reference/api/materials/rating/) and [`materials.absorbers.uncertainty`](https://docs.jmrp.io/phonometry/reference/api/materials/uncertainty/).
- Theory: [Acoustic material characterisation](https://docs.jmrp.io/phonometry/reference/theory/materials-surfaces/#acoustic-material-characterisation-iso-11654-iso-9053-12-iso-10534-12-astm-e2611): the ISO 354 decay difference, the ISO 11654 rating and where the practical coefficients come from.
- [Published catalogues](https://docs.jmrp.io/phonometry/reference/catalogues/absorption-coefficients/): the
  band-by-band absorption coefficients the books print, with the mounting each
  one was measured on.

## Quick answers

### What weighted absorption coefficient does each ISO 11654 class need?

`materials.absorption_class(alpha_w)` reads Table B.1 of ISO 11654, and
`weighted_absorption` hands back the same letter as `absorption_class` beside
the rating itself. The weighted coefficient $\alpha_\mathrm{w}$ moves in fixed
steps, so each class is a run of steps, and the loop below prints the lowest
step of each class beside the step under it: class A starts at `0.9`, B at
`0.8`, C at `0.6`, D at `0.3` and E at `0.15`, and below that a product is
`Not classified`.

```python
from phonometry import materials

for lowest in (0.9, 0.8, 0.6, 0.3, 0.15):
    below = round(lowest - 0.05, 2)
    print(lowest, materials.absorption_class(lowest), below, materials.absorption_class(below))
# 0.9 A 0.85 B
# 0.8 B 0.75 C
# 0.6 C 0.55 D
# 0.3 D 0.25 E
# 0.15 E 0.1 Not classified
```

## References

- **Cox, T. J., & D'Antonio, P. (2017).** *Acoustic absorbers and diffusers: Theory, design and application* (3rd ed.). CRC Press. https://doi.org/10.1201/9781315369211
  Absorber measurement in practice: the room method, mountings, and the edge-effect discussion behind the tube-or-reverberation-room section. ISBN 978-1-4987-4099-9.
- **International Organization for Standardization. (1997).** [*Acoustics — Sound absorbers for use in buildings — Rating of sound absorption*](https://www.iso.org/standard/19583.html) (ISO 11654:1997).
  The weighted sound-absorption rating of section 3: the practical coefficient, the shifted reference curve, the shape indicators and the absorption class, validated against the standard's own Annex A worked example.
- **International Organization for Standardization. (2003).** [*Acoustics — Measurement of sound absorption in a reverberation room*](https://www.iso.org/standard/34545.html) (ISO 354:2003).
  The reverberation-room method of section 1 that produces the alpha_s spectra rated by ISO 11654, including the Annex B specimen mountings.
- **International Organization for Standardization. (2020).** [*Acoustics — Determination and application of measurement uncertainties in building acoustics — Part 2: Sound absorption*](https://www.iso.org/standard/68749.html) (ISO 12999-2:2020).
  The sound-absorption measurement uncertainty of section 4, validated against the standard's own worked examples (Tables 4/5).