# Sound Power in a Duct

> One page of the phonometry documentation, as Markdown. Index: https://docs.jmrp.io/phonometry/llms.txt

Canonical: https://docs.jmrp.io/phonometry/devices/emission/sound-power-in-duct/
Language: en
Alternate: https://docs.jmrp.io/phonometry/es/devices/emission/sound-power-in-duct/index.md
Version: phonometry 4.0.0
Install: pip install "phonometry[full]"
Author: José Manuel Requena Plens (https://orcid.org/0000-0003-1250-6212)
Published: 2026-09-02
Updated: 2026-10-21T12:42:46Z
Standards: ISO 5136:2003
Verified: 6 conformance checks (ISO 5136:2003) https://docs.jmrp.io/phonometry/reference/conformance/#intensity-sound-power
License: MIT (https://github.com/jmrplens/phonometry/blob/main/LICENSE)
Summary: Fan sound power by the ISO 5136 in-duct method: averaged level, the C1, C2 and C3,4 corrections, the A-weighted total and reproducibility.

---

A ducted fan does not radiate into a room. What leaves it travels down the
duct it is bolted to, and a hemisphere of microphones around the casing would
measure the casing, not the fan. ISO 5136 therefore measures *inside* the
duct: the fan is connected to an anechoically terminated test duct on its
inlet and/or outlet side, a microphone samples the one-third-octave level in
that duct, and the sound power follows from the plane-wave relation between
pressure and power in a pipe of known cross-section. What makes the method
more than that one relation is the microphone's situation. It sits in a mean
flow of up to 40 m/s, which fills it with turbulent pressure fluctuations that
are not sound, so it is shielded by a sampling tube, a nose cone or a foam
ball; the shield has a response of its own; and above the first cut-on the
duct carries higher-order modes to which a sampling tube does not respond as
it does to a plane wave. This guide covers the three corrections that put
those effects back, the plane-wave relation, the A-weighted total and the
uncertainty the standard says to record. Which route fits which job, and the
room and intensity alternatives for a machine that can be unducted, are
weighed in [Sound Power](https://docs.jmrp.io/phonometry/devices/emission/sound-power/).

## 1. The in-duct method (ISO 5136)

The test duct is circular, **0.15 m to 2 m** in diameter (clause 1.1), joined
to the fan through a transition and a flow straightener and closed by an
anechoic termination whose reflection coefficient the facility has to
qualify (Table 5). The microphone stands at a fixed radius, $2r/d$ of 0.8 in
ducts under 0.5 m and 0.65 from 0.5 m up for the sampling tube, 0.5 for the
omni-directional shields (Table 7), pointing at the fan, and reads the
time-averaged level at **three circumferential positions** 120° apart, or
by multiplexing between them, or over one continuous revolution taking at
least 30 s (clauses 6.2.2 and 7.2). Each reading averages over at least 30 s
in the bands at and below 160 Hz and 10 s above (clause 7.2.2), and must
stand at least 6 dB above the background and above the turbulence noise the
shield lets through (clause 7.2.1, Annex B).

![Side section of a fan on the ISO 5136 rig, measured in both its ducts at once. Air enters at the left through a bell mouth and an anechoic termination into the inlet test duct, marked U less than 0, and passes a transition and an intermediate duct to the fan. From there it runs through an intermediate duct with a straight run on each side of a star flow straightener two diameters long, then a transition into the outlet test duct, marked U greater than 0, which ends in a second anechoic termination with the throttle at its far end. In each test duct a microphone in a sampling tube hangs from the wall and points back at the fan. Dimensions under each test duct, from its fan-side end: at least four diameters and 2 m to the measurement plane, at least six diameters and 4 m for the whole duct. Below, three panels: the measurement plane seen along the duct, with three microphone positions 120 degrees apart at radius r, 2r/d being 0.65 from 0.5 m, 0.8 below it and 0.5 for a nose cone or foam ball, so a 0.63 m duct puts r at 0.20 m; the sampling tube, with its nose cone, porous slit and microphone, at most 22 mm across; and the three ways to the mean around the duct with their averaging times. A box at the foot carries Equations 9 to 12, the energy mean of three or more readings, the same level from a multiplexed or traversed reading, and the step to sound power, and three lines under it the instruments, the 6 dB margins, the reflection coefficient of the termination and the reading with and without the straightener](https://docs.jmrp.io/phonometry/media/diagram_in_duct_rig.svg)

Clause 8 turns the readings into a level and the level into a power. The
positions are energy-averaged and the combined correction $C$ added
(Eqs 9 and 10), a multiplexed or traversed level takes the correction
directly (Eq. 11), and the plane-wave relation does the rest (Eq. 12):

$$
\overline{L_p} = 10 \lg\left[\frac{1}{n}\sum_{i=1}^{n} 10^{0.1 L_{pi}}\right]
+ C, \qquad C = C_1 + C_2 + C_{3,4},
$$

$$
L_W = \overline{L_p} + 10 \lg\frac{S}{S_0} - 10 \lg\frac{\rho c}{(\rho c)_0},
\qquad S = \frac{\pi d^2}{4},\quad S_0 = 1\ \mathrm{m^2},\quad
(\rho c)_0 = 400\ \mathrm{N \cdot s/m^3}.
$$

The three corrections are of different kinds. $C_1$ is the microphone's
free-field correction, taken from the manufacturer's data. $C_2$ is the
frequency response of the shield at normal incidence, measured on the
individual tube or cone in a plane-wave field to within ±0.5 dB
(clauses 5.3.3.2 c) and 5.3.4.2); the standard tabulates neither, so both
are inputs here, per band or as a scalar. $C_{3,4}$, the **combined mean
flow velocity and modal correction**, is the one the standard computes. For
the sampling tube it is a polynomial in the mean flow velocity $U$ at the
microphone, in metres per second, negative on the inlet side and positive
on the outlet side (clause 5.3.3.4, Eq. 7):

$$
C_{3,4} = \sum_{i=0}^{10} a_i U^i ,
$$

with the coefficients $a_i$ tabulated in Annex A per one-third-octave band
and per range of duct diameter (Tables A.1 to A.6), an empty cell counting
as zero. The tables are normative for 50 Hz to 10 kHz and $|U| \le 40$ m/s,
and their footnote adds two informative extensions that do not compose: the
50 Hz to 10 kHz rows also hold from 40 m/s to 60 m/s, while the 12.5 kHz to
20 kHz rows sit under a band header of their own that reads $|U| \le 40$ m/s
and get no velocity extension, so `sound_power_in_duct()` refuses a velocity
past 40 m/s as soon as a band above 10 kHz is asked for. For the nose cone
and the foam ball no modal data exist, and
clause 5.3.4.3 replaces the polynomial by the frequency-independent
convective term of Eq. 8, $C_{3,4} = 10 \lg[1/(1 - U/c)^2]$, where $c$ is
the speed of sound in the test duct; clause 5.3.4.3 prints 340 m/s "under
normal conditions", which is what `flow_modal_correction()` uses on its own,
while a whole determination knows the duct air and evaluates Eq. 8 with the
$c$ that `temperature_c` gives, up to 0.08 dB away over the range of
clause 1.1. The same sign convention applies, so
it is positive on the outlet side and negative on the inlet side, a few
tenths of a decibel at the velocities those shields are allowed (15 m/s for
the foam ball, 20 m/s for the nose cone, clause 1.1).

![Two panels. On the left, the sampling-tube correction C3,4 of ISO 5136 for a 0.5 m test duct against frequency from 50 Hz to 20 kHz, six curves for mean flow velocities of plus and minus 5, 15 and 30 metres per second: all six stay inside 1.6 dB of zero up to 500 Hz, the inlet-side curve at minus 30 metres per second dipping to minus 1.5 dB at 315 Hz, then they climb with frequency, the outlet-side curves faster than the inlet-side ones, reaching 24 dB at 20 kHz and plus 30 metres per second while the inlet-side curve at minus 30 reaches 8 dB; a dotted line marks the top of the 10 kHz band, beyond which a chip notes that the values are for information only. On the right, the same correction against the flow velocity from minus 40 to plus 40 metres per second in the 1 kHz, 4 kHz and 10 kHz bands, three curves that rise from the inlet side to the outlet side, the 10 kHz one from 6 dB to 19 dB, with the nose cone and foam ball correction of Equation 8 drawn dashed between minus 20 and plus 20 metres per second and never further than 0.53 dB from zero](https://docs.jmrp.io/phonometry/media/in_duct_flow_correction.svg)

*What the sampling tube costs and where. In a 0.5 m duct the correction
stays within 1.6 dB of zero below 500 Hz, where the duct carries plane waves,
and climbs to 10 dB and more above 4 kHz, where the higher-order modes reach
the microphone from every direction and the slit tube, which listens along
its axis, hears less of them. The polynomial is not odd in $U$: the same
30 m/s corrects the outlet side by 24 dB at 20 kHz and the inlet side by 8 dB,
because the flow carries the modes towards the microphone on one side and
away from it on the other. The omni-directional shields have no modal
correction at all, only the convective term, which is why they are confined
to the low velocities of clause 1.1.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import emission

# A 0.5 m test duct on both sides of the fan: U > 0 on the outlet side,
# U < 0 on the inlet side, the nominal one-third-octave bands of the standard.
bands = np.array([50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
                  1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000, 6300, 8000,
                  10000, 12500, 16000, 20000], dtype=float)
fig, (axf, axu) = plt.subplots(1, 2, figsize=(12.5, 5.6))
for speed in (5.0, 15.0, 30.0):
    for sign, style, side in ((1.0, "-", "Outlet"), (-1.0, "--", "Inlet")):
        c34 = emission.flow_modal_correction(bands, sign * speed, 0.5)
        axf.semilogx(bands, c34, style, marker="o",
                     label=f"{side}, U = {sign * speed:+.0f} m/s")
axf.set(xlabel="Frequency [Hz]", ylabel="Correction C3,4 [dB]")
axf.legend()

# The same correction against the flow velocity, and Eq. 8 for the nose cone.
speeds = np.linspace(-40.0, 40.0, 161)
for band in (1000.0, 4000.0, 10000.0):
    c34 = [float(emission.flow_modal_correction([band], u, 0.5)[0]) for u in speeds]
    axu.plot(speeds, c34, label=f"{band / 1000:g} kHz")
cone_speeds = np.linspace(-20.0, 20.0, 81)
cone = [float(emission.flow_modal_correction([1000.0], u, 0.5, shield="nose-cone")[0])
        for u in cone_speeds]
axu.plot(cone_speeds, cone, "--", label="Nose cone, Eq. 8")
axu.set(xlabel="Mean flow velocity U [m/s]", ylabel="Correction C3,4 [dB]")
axu.legend()
plt.show()
```

### How the measurement goes

Build the airway first. Each test duct is straight, circular and coaxial with
the fan, at least six diameters and 4 m long, with the measurement plane at
least four diameters and 2 m from its fan-side end, ending in an anechoic
termination within Table 5. The throttle goes beyond it, at least 10 dB quieter
than the fan. Set the operating point by ISO 5801 and check the type 1 chain
with a class 1 calibrator on the bare microphone before and after each series.
Mount the sampling tube vibration-isolated from the duct wall, at the radius of
Table 7, aligned with the axis to ±5° and pointing at the fan, with its
microphone end rounded on the inlet side, and take the mean round the duct:
three or more equally spaced positions for at least 30 s up to 160 Hz and 10 s
from 200 Hz, multiplexing for 30 s a band, or one revolution of 30 s or more.
Every band has to stand at least 6 dB above the background with the fan
stopped, and above the turbulence of Annex B; where it does not, report it as
measured, uncorrected, with the note of clause 7.2.1. On the outlet side,
measure with and without the star straightener at the same operating point and
keep the lower level in each band. The report states compliance, gives the
levels in decibels re 1 pW, names the fan, its operating conditions, the
instruments, the shield and any agreed options, and should quote $2\sigma_R$ as
the uncertainty.

## 2. A ducted fan on its outlet duct

The example is a 630 mm axial fan measured on its outlet test duct with a
sampling tube, at a mean flow velocity of 12 m/s, about 3.7 m³/s. The three
positions are read in the 24 bands from 50 Hz to 10 kHz; the microphone's
free-field correction and the sampling tube's own response come from their
calibration sheets, both growing towards the top of the range.

```python
import numpy as np
from phonometry import emission

freqs = np.array([50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
                  1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000, 6300, 8000,
                  10000], dtype=float)
# The mean in-duct spectrum of the fan (dB re 20 uPa): the broadband hump of
# an axial fan around 250 Hz to 500 Hz, and the blade-passage tone of six
# blades at 1 450 r/min, 145 Hz, in the 160 Hz band.
mean = np.array([78.0, 79.5, 81.0, 82.5, 84.0, 88.0, 85.5, 86.0, 86.5, 86.0,
                 85.0, 84.0, 83.0, 82.0, 80.5, 79.0, 77.5, 76.0, 74.0, 72.0,
                 70.0, 67.5, 65.0, 62.0])
# Three circumferential positions 120 degrees apart, each a few tenths off it.
spread = np.array([[0.4], [-0.3], [-0.1]]) + 0.3 * np.sin(
    np.arange(freqs.size) * np.array([[1.0], [1.7], [2.3]]))
levels = mean + spread                                   # shape (3, 24)
c1 = np.array([0.0] * 19 + [0.1, 0.2, 0.4, 0.7, 1.1])    # microphone, dB
c2 = np.array([0.0] * 11 + [0.2, 0.3, 0.5, 0.6, 0.8, 1.0, 1.2, 1.5, 1.9,
                            2.3, 2.8, 3.4, 4.0])         # sampling tube, dB

duct = emission.sound_power_in_duct(
    levels, frequencies=freqs, duct_diameter_m=0.63, flow_velocity=12.0,
    shield="sampling-tube", microphone_correction=c1, shield_correction=c2,
    temperature_c=20.0, static_pressure_kpa=101.325,
)
print(round(float(duct.mean_pressure_level[5]), 1))       # 87.9 dB at 160 Hz
print(round(float(duct.flow_modal_correction[13]), 2))    # C3,4 = 2.31 dB at 1 kHz
print(round(float(duct.combined_correction[23]), 1))      # C = 18.0 dB at 10 kHz
print(round(float(duct.sound_power_level[5]), 1))         # LW = 83.0 dB at 160 Hz
print(round(duct.sound_power_level_a, 1))                 # LWA = 89.7 dB(A)
print(round(duct.duct_area, 3), round(duct.characteristic_impedance, 1))  # 0.312 m2, 413.3 N s/m3

duct.plot()   # in-duct LW spectrum, LWA in the title (needs matplotlib)
```

![Bar chart of the in-duct sound power level of the example fan in the 24 one-third-octave bands from 50 Hz to 10 kHz, with the A-weighted total of 89.7 decibels in the title. The bars rise from 73 dB at 50 Hz to 83 dB at 160 Hz, the blade-passage band, then sit between 79 and 81 dB up to 1.25 kHz and fall gently to 75 dB at 10 kHz. A dashed line with circular markers traces the measured in-duct level before the corrections: it is 5 dB above the bars at the low end, crosses them near 2 kHz and ends 13 dB below them at 10 kHz, where the sampling-tube corrections are largest](https://docs.jmrp.io/phonometry/media/sound_power_in_duct_result.svg)

*The bars are $L_W$ per band, the dashed line the level the sampling tube
read before any correction. At the low end the two differ by 4.93 dB: the
area term $10 \lg S = -5.06$ dB for the 0.312 m² duct, and the $-0.14$ dB of
the impedance term, which widens the gap rather than closing it because
Eq. (12) subtracts it, less the
0.27 dB that $C_{3,4}$ already adds at 12 m/s even in the plane-wave bands.
From 1 kHz up the corrections take over, until at 10 kHz the combined
correction reaches 18 dB (4.0 dB of tube response, 12.9 dB of $C_{3,4}$ and
1.1 dB of microphone correction) and the power exceeds the reading by 13 dB.
A spectrum read in a duct without these corrections is not the fan's
spectrum.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt

# duct is the InDuctSoundPowerResult computed above. One line:
duct.plot()
plt.show()

# By hand: the LW bars with the uncorrected in-duct level beside them.
positions = np.arange(freqs.size)
fig, ax = plt.subplots(figsize=(10, 6.3))
ax.bar(positions, duct.sound_power_level, width=0.7, label="Sound power level LW")
ax.plot(positions, duct.mean_pressure_level, "o--",
        label="Measured in-duct level, before the corrections")
ax.set_xticks(positions)
ax.set_xticklabels([f"{f:g}" for f in freqs], rotation=45, ha="right")
ax.set_xlabel("Frequency [Hz]")
ax.set_ylabel("Level [dB]")
ax.set_title(f"In-duct sound power (ISO 5136)  LWA = {duct.sound_power_level_a:.1f} dB(A)")
ax.legend()
plt.show()
```

Two things in that determination are worth reading off the result rather
than assuming. The first is the sign of $U$. The same three spectra read on
the *inlet* duct of the same fan, at the same 12 m/s, carry a smaller
correction, 1.39 dB instead of 2.31 dB at 1 kHz, and come out 1.6 dB(A)
lower:

```python
inlet = emission.sound_power_in_duct(
    levels, frequencies=freqs, duct_diameter_m=0.63, flow_velocity=-12.0,
    microphone_correction=c1, shield_correction=c2,
)
print(round(float(inlet.flow_modal_correction[13]), 2))   # 1.39 dB at 1 kHz
print(round(inlet.sound_power_level_a, 1))                # 88.1 dB(A)
```

The second is what the omni-directional shields do not correct. A nose cone
at the same 12 m/s takes the convective 0.31 dB of Eq. 8 in every band and
nothing else, so the same readings give 86.6 dB(A), 3 dB less than through
the sampling tube. The readings are reused unchanged only to isolate what the
correction does; a nose cone in that duct would not read them. It is
omni-directional, so it hears the higher-order modes the slit tube turns away
from, and more of the turbulence, and its in-duct level would come out
higher, which is why the standard warns in clause 5.3.4.3 that the level
obtained with a nose cone or foam ball "is expected to be higher than the
true sound power level". The missing modal correction is the reason the two
shields are limited to low velocities and the sampling tube is preferred
(clause 4, NOTE 5).

The same NOTE 5 also says the uncertainties of Table 2 "refer to the sampling
tube only and can be expected to increase for other shields", and it puts no
number on the increase. So the reproducibility a nose cone or a foam ball
result carries is the sampling tube's, which makes it a lower bound rather
than that shield's own figure, and the call says so with a
`SoundPowerWarning` rather than leave it to be read off a table.

```python
cone = emission.sound_power_in_duct(
    levels, frequencies=freqs, duct_diameter_m=0.63, flow_velocity=12.0,
    shield="nose-cone", microphone_correction=c1,
)
print(round(float(cone.flow_modal_correction[0]), 2))     # 0.31 dB, every band
print(round(cone.sound_power_level_a, 1))                 # 86.6 dB(A)
```

### `sound_power_in_duct()` parameters

| Parameter | Type | Units | Range / default | Notes |
| :--- | :--- | :--- | :--- | :--- |
| `levels` | 1D or 2D array | dB | `(bands,)` or `(positions, bands)` | Time-averaged in-duct SPL; 2D is energy-averaged over the positions (Eq. 9), 1D is a multiplexed or traversed level (Eq. 11) |
| `frequencies` | 1D array | Hz | nominal thirds, 50 Hz to 20 kHz | Required: the coefficients, the A-weighting and $\sigma_R$ are all keyed by the nominal centre |
| `duct_diameter_m` | float | m | 0.15 to 2 | Test-duct diameter $d$ (clause 1.1); selects the Annex A table |
| `flow_velocity` | float | m/s | signed; ≤ 40 sampling tube (60 for information, but ≤ 40 whenever a band above 10 kHz is asked for), ≤ 20 nose cone, ≤ 15 foam ball | Mean flow velocity $U$ at the microphone; negative on the inlet side |
| `shield` | str | | `'sampling-tube'` (default), `'nose-cone'`, `'foam-ball'` | Selects Eq. 7 with Annex A or Eq. 8, and the velocity limit |
| `microphone_correction` | float or 1D array | dB | default `0.0` | $C_1$ from the manufacturer's data |
| `shield_correction` | float or 1D array | dB | default `0.0` | $C_2$ measured per 5.3.3.2 c) or 5.3.4.2 |
| `temperature_c` | float | °C | −50 to 70, default `20.0` | Duct air; sets $c$ and $\rho$, and with them the $c$ of Eq. 8 for the omni-directional shields |
| `static_pressure_kpa` | float | kPa | default `101.325` | Duct air; sets $\rho$ |

The function returns an `InDuctSoundPowerResult` with the band $L_W$
(`sound_power_level`), the A-weighted total of Annex C
(`sound_power_level_a`), the level before and after the correction
(`mean_pressure_level`, `corrected_pressure_level`), the three corrections and
their sum (`microphone_correction`, `shield_correction`,
`flow_modal_correction`, `combined_correction`), the uncertainty statement of
the next section (`reproducibility_standard_deviation`,
`expanded_uncertainty`, `information_only_band`) and the geometry and air it
was computed with (`duct_diameter_m`, `duct_area`, `characteristic_impedance`,
`speed_of_sound`, `flow_velocity`, `shield`). `flow_modal_correction()` gives
$C_{3,4}$ on its own for any band, velocity, diameter and shield, and
`in_duct_reproducibility()` the $\sigma_R$ of the next section.

## 3. The uncertainty to be recorded

ISO 5136 states no accuracy grade. What it states is the **standard deviation
of reproducibility** $\sigma_R$ of the method, band by band, for the sampling
tube (clause 4, Table 2): 3.5 dB at 50 Hz, 3 dB at 63 Hz, 2.5 dB at 80 Hz and
100 Hz, 2 dB from 125 Hz to 4 kHz, then 2.5, 3, 3.5 and 4 dB at 5 kHz,
6.3 kHz, 8 kHz and 10 kHz. These are inter-laboratory figures, the spread
expected if one fan were measured in many facilities, and they include the
duct end reflections, the transitions, the calibration and the sampling; they
do not include the fan's own variation with its mounting. Unless the
laboratory knows better, clause 9.2 says to record twice that figure as the
expanded uncertainty at 95 % coverage, and that is what the result carries:

```python
print(duct.reproducibility_standard_deviation[[0, 13, 23]])   # [3.5 2.  4. ] dB
print(duct.expanded_uncertainty[[0, 13, 23]])                 # [7. 4. 8.] dB
print(bool(duct.information_only_band.any()))                 # False
```

Three caveats travel with those numbers, and the result says so where it
can. Table 2 is stated for the sampling tube; clause 4 NOTE 5 expects the
figures to be larger for the nose cone and the foam ball and gives no others,
so a determination through those shields carries the same values and the
caveat. Above 10 kHz the standard is explicit that measurements "are not
considered part of this International Standard", and only suggests the
extrapolated 4.5, 5 and 5.5 dB of Table 3; the Annex A coefficients are
likewise for information only there, and between 40 m/s and 60 m/s. Every
band in that position is flagged in `information_only_band`. And the figures
assume the time averages of clause 7.2.2 and no strong discrete tones
(NOTE 4); a fan with a dominant blade-passage tone in a low band, like the
one above, will reproduce worse than 2 dB in that band.

## What this guide covers

- **Covered.** The ISO 5136:2003 in-duct determination (`sound_power_in_duct`): the energy
  average over the circumferential positions (Eq. 9) or the multiplexed level
  (Eq. 11), the combined correction $C = C_1 + C_2 + C_{3,4}$ (Eq. 10) with the
  Annex A polynomial of the sampling tube for 0.15 m to 2 m ducts
  (`flow_modal_correction`, Tables A.1 to A.6, verified against every cell of
  Table D.1) and the convective term of Eq. 8 for the nose cone and foam ball,
  the plane-wave relation of Eq. 12 with the duct air's $\rho c$, the A-weighted
  total of Annex C over the 27 bands of Table C.1, and the reproducibility of
  Table 2 doubled into the 95 % statement of clause 9.2
  (`in_duct_reproducibility`), with the bands the standard gives for
  information only flagged as such.

- **Not covered.** The facility and the instrument are assumed qualified. The reflection
  coefficient of the anechoic termination (Table 5, Annex F), the directivity
  limits of the sampling tube (Eq. 6, Table 6), the signal-to-noise check
  against turbulence (Annex B, Tables B.1 and G.1), the duct geometry and
  transitions of clause 5.2 and the swirl angle of Annex J are checks the
  laboratory makes, not terms of $L_W$, and none of them is computed. $C_1$
  and $C_2$ are inputs: the standard tabulates neither, only how to measure
  them. The informative Annexes H and I, which extend the coefficient tables
  below 0.15 m and above 2 m, are outside the standard's own scope and are not
  implemented, so a duct outside 0.15 m to 2 m is refused.

## See also

- [Sound Power](https://docs.jmrp.io/phonometry/devices/emission/sound-power/): choosing among the
  determination routes, the accuracy grades and the ISO 4871 noise-emission
  declaration a measured $L_{W\mathrm{A}}$ feeds.
- [Sound Power by Pressure Methods (ISO 3744 / ISO 3746 / ISO 3745)](https://docs.jmrp.io/phonometry/devices/emission/sound-power-pressure/):
  the enveloping surface, for a fan that can be run unducted.
- [Sound Power in the Reverberation Room (ISO 3741)](https://docs.jmrp.io/phonometry/devices/emission/sound-power-reverberation/):
  the diffuse-field route for a machine small enough to travel.
- [Duct acoustics](https://docs.jmrp.io/phonometry/devices/noise-control/duct-path/): the higher-order
  duct modes whose cut-on bounds the plane-wave range of Eq. 12.
- [Levels](https://docs.jmrp.io/phonometry/signals/levels/levels/): energy averaging and the
  A-weighting behind $L_{W\mathrm{A}}$.
- API reference: [`emission`: sound power in a duct](https://docs.jmrp.io/phonometry/reference/api/power/sound-power-in-duct/).

## References

- **Arnold, F. (1999).** *Experimentelle und numerische Untersuchung zur Schalleistungsbestimmung in Strömungskanälen*. VDI Verlag.
  Fortschritt-Berichte VDI, Reihe 7, Nr. 353 (Dissertation, TU Berlin, 1998). Reference \[24\] of ISO 5136, the source of the combined mean flow velocity and modal correction of the sampling tube and of its Annex A coefficients.
- **International Organization for Standardization. (2003).** [*Acoustics — Determination of sound power radiated into a duct by fans and other air-moving devices — In-duct method*](https://www.iso.org/obp/ui/#iso:std:iso:5136:ed-2:v1:en) (ISO 5136:2003).
  Clause 8 (Eqs 9 to 12), the corrections of 5.3.3 and 5.3.4 with the Annex A coefficients and the Annex D example, the A-weighting of Annex C and the reproducibility of Table 2 that this guide implements.