# Room acoustic parameters (ISO 3382-1/2)

> One page of the phonometry documentation, as Markdown. Index: https://docs.jmrp.io/phonometry/llms.txt

Canonical: https://docs.jmrp.io/phonometry/buildings/rooms/room-acoustics/
Language: en
Alternate: https://docs.jmrp.io/phonometry/es/buildings/rooms/room-acoustics/index.md
Version: phonometry 4.0.0
Install: pip install "phonometry[full]"
Author: José Manuel Requena Plens (https://orcid.org/0000-0003-1250-6212)
Published: 2026-07-07
Updated: 2026-11-16T21:36:13Z
Standards: ISO 3382-1:2009; ISO 3382-2:2008
Verified: 23 conformance checks (ISO 3382-1:2009; ISO 3382-2:2008) https://docs.jmrp.io/phonometry/reference/conformance/#room-building-acoustics
License: MIT (https://github.com/jmrplens/phonometry/blob/main/LICENSE)
Summary: Decay analysis of a room impulse response in Python by ISO 3382-1/2: Schroeder curve, EDT, T20, T30, clarity, definition, centre time and the fiche.

---

Room acoustics starts from one measurement: the **impulse response** (IR)
between a source and a receiver. Filter it into bands and integrate it, and
it yields reverberation time, clarity and centre time: everything
ISO 3382-1/2 asks about the sound field inside a single room. This page
turns a measured IR into those parameters: the Schroeder decay curve, the
evaluation windows, the validity flags and the accredited fiche. Acquiring
the IR itself (sweeps, MLS, where to measure) lives in
[Measuring the Room Impulse Response](https://docs.jmrp.io/phonometry/buildings/rooms/room-impulse-response/),
and the open-plan speech metrics of ISO 3382-3 in
[Open-Plan Office Acoustics](https://docs.jmrp.io/phonometry/buildings/rooms/open-plan-acoustics/). Two
separate decay measurements in a reverberation room, one with the room empty
and one with the specimen installed, yield a material's sound absorption;
that method (ISO 354) lives in
[Sound Absorption Measurement and Rating](https://docs.jmrp.io/phonometry/materials/absorbers/absorption-measurement/).
For sound insulation *between* spaces (the same IR measured either side of a
partition) see the companion
[Field Insulation Measurement (ISO 16283) guide](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-field/).

## How do I compute EDT, T20 and T30 from an impulse response in Python?

Pass the impulse response and its sample rate to
`room.room_parameters(ir, fs)`. It splits the response into octave bands
(`fraction=3` gives one-third octaves), integrates each band backwards into its
Schroeder decay curve and fits the evaluation range of each parameter, so
`res.edt`, `res.t20` and `res.t30` hold one decay time in seconds per band,
with the clarity `c50` and `c80`, the definition `d50` and the centre time `ts`
beside them. `res.t30_valid` says, band by band, whether the noise floor left
the fit enough decay range. On the stand-in response below, the octave values
of `res.t30` average to `1.21` s. What it means when EDT, T20 and T30
disagree is in
[Reading EDT, T20 and T30 against each other](#reading-edt-t20-and-t30-against-each-other).

```python
import numpy as np
from phonometry import room

# ir: your measured impulse response, sampled at fs hertz. Two seconds of noise
# decaying with a reverberation time of 1.2 s stand in for it here.
fs = 48000
t = np.arange(2 * fs) / fs
ir = np.random.default_rng(1).standard_normal(t.size) * np.exp(-3 * np.log(10) / 1.2 * t)

res = room.room_parameters(ir, fs)
print(res.frequencies.round())        # [ 126.  251.  501. 1000. 1995. 3981.]
print(res.edt.round(2))               # [1.16 1.29 1.16 1.12 1.19 1.17] s
print(res.t20.round(2))               # [1.18 1.24 1.21 1.25 1.24 1.2 ] s
print(res.t30.round(2))               # [1.2  1.19 1.23 1.21 1.21 1.21] s
print(res.t30_valid.all())            # True
print(round(float(res.t30.mean()), 2))  # 1.21 s
```

## Decay analysis and room parameters (ISO 3382-1/2)

The IR is filtered into octave (or one-third-octave) bands and each band is
turned into a **decay curve** by Schroeder backward integration of the
squared IR:

$$
E(t) = \int_t^{\infty} p^2(\tau)\ d\tau, \qquad
L(t) = 10 \log_{10} \frac{E(t)}{E(0)}\ \text{dB}.
$$

Integrating *backwards* removes the fluctuation that plagues a raw squared
IR and yields a smooth curve whose slope is the decay rate. Background
noise would make $E(t)$ level off, so integration is truncated where the
fitted decay line crosses the noise floor and the missing tail is
compensated assuming an exponential decay.

Reverberation times come from a least-squares line fit over an evaluation
range, extrapolated to a full 60 dB drop, $T = -60/\text{slope}$:
**EDT** over 0 to −10 dB (perceived reverberance), **T20** over −5 to −25 dB
and **T30** over −5 to −35 dB. Energy splits at an early/late boundary give
**clarity** and **definition**,

$$
C_{te} = 10 \log_{10} \frac{\int_0^{te} p^2\ dt}{\int_{te}^{\infty} p^2\ dt}\ \text{dB}, \qquad
D_{50} = \frac{\int_0^{0.05} p^2\ dt}{\int_0^{\infty} p^2\ dt},
$$

with $te = 50$ ms → C50 (speech) and $te = 80$ ms → C80 (music), plus the
**centre time** $T_\mathrm{S} = \int t\ p^2\ dt / \int p^2\ dt$. Each parameter has a
**just-noticeable difference** (ISO 3382-1 Table A.1: EDT 5 %, C80 1 dB,
D50 0.05, Ts 10 ms) that sets how precisely it is worth reporting.

**Where $t = 0$ is.** All three energy integrals start at the arrival of the
**direct sound**, not at the start of the file. ISO 3382-1 A.3.4 places that
point where the response first rises significantly above the background while
still being more than 20 dB below its maximum, and `room_parameters` applies
that trigger per band before integrating, so any propagation and system delay
carried by the recording is removed automatically. A measured IR needs no
manual trimming. It matters asymmetrically. The reverberation times use only the
*slope* of the decay and are indifferent to where it starts, but C50, C80 and
$T_\mathrm{S}$ integrate *from* $t = 0$, so an onset placed one millisecond late throws
away part of the direct sound and can move C50 and C80 by several decibels and
$T_\mathrm{S}$ by tens of milliseconds, while leaving T20 and T30 almost untouched. The
error is invisible in the number everyone checks. The detector deliberately errs
early, which is the harmless direction. Two working rules follow: never trim an
IR by hand to remove its pre-delay, and be suspicious of C50/C80 from a
recording whose direct sound is soft or has been pre-ringed by external
processing, because the trigger can then fire late.

**Video:** [Schroeder backward integration of the squared impulse response](https://docs.jmrp.io/phonometry/media/anim_schroeder.webm): The tail energy of the squared impulse response fills from the end while the backward integral advances toward t = 0, and the Schroeder decay curve emerges on a companion axis, ending with the T20 and T30 regression lines.

![Squared impulse response with its Schroeder backward-integrated decay curve, and the EDT, T20 and T30 regression windows marked](https://docs.jmrp.io/phonometry/media/schroeder_decay.webp)

*The jagged squared IR (grey) integrates to the smooth Schroeder curve
(blue); the EDT, T20 and T30 windows are fitted on that curve and each
extrapolated to a 60 dB decay.*

```python
import numpy as np
from phonometry import room

fs = 48000
# Single-slope decay with T = 1 s: p^2 = exp(-13.8155 t)  (60/ln(10)/13.8155 = 1)
t = np.arange(fs) / fs
# ir: measured room impulse response; a synthetic single-slope decay stands in here.
ir = np.concatenate([np.zeros(10), np.exp(-13.8155 * t / 2.0)])

decay = room.decay_curve(ir, fs)          # Schroeder curve (0 dB at t = 0)
time, level = decay.times, decay.levels

res = room.room_parameters(ir, fs, limits=None)           # broadband single band
print(round(float(res.t30[0]), 2))                   # 1.0  s
print(round(float(res.c80[0]), 2))                   # 3.05 dB
print(round(float(res.d50[0]), 3))                   # 0.499
print(round(float(res.ts[0]) * 1000, 0))             # 72 ms

# Octave bands 125 Hz - 4 kHz (ISO 3382-1 default); use fraction=3 for thirds
octaves = room.room_parameters(ir, fs)
print(octaves.frequencies)                             # ~[126, 251, 501, 1000, 1995, 3981]
print(octaves.t30_valid)                             # per-band dynamic-range flags

octaves.plot()               # per-band EDT/T20/T30 + C50/C80 bars (needs matplotlib)
room.decay_curve(ir, fs).plot()   # Schroeder decay with EDT/T20/T30 fit overlays
```

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import room

fs = 48000
# Single-slope decay with T = 1 s: p^2 = exp(-13.8155 t)  (60/ln(10)/13.8155 = 1)
t = np.arange(fs) / fs
# ir: measured room impulse response; a synthetic single-slope decay stands in here.
ir = np.concatenate([np.zeros(10), np.exp(-13.8155 * t / 2.0)])
decay = room.decay_curve(ir, fs)          # Schroeder curve (0 dB at t = 0)
time, level = decay.times, decay.levels

# One line — Schroeder decay with the EDT/T20/T30 straight-line fits:
decay = room.decay_curve(ir, fs)          # a DecayCurve: read decay.times and decay.levels
decay.plot()
plt.show()

# By hand, the decay is just the Schroeder curve; mark the evaluation levels:
fig, ax = plt.subplots()
ax.plot(time, level, color="#1f77b4", label="Schroeder decay")
for db in (-5.0, -25.0, -35.0):      # T20 / T30 evaluation-window edges
    ax.axhline(db, ls=":", alpha=0.4)
ax.set_xlabel("Time [s]")
ax.set_ylabel("Level re steady state [dB]")
ax.set_ylim(top=3.0)
ax.legend()
plt.show()
```

For this single-slope decay EDT, T20 and T30 all return ≈ 1.0 s, and the
energy parameters match their closed forms (C80 = 3.05 dB, D50 = 0.499,
Ts = 72 ms). A real room has a steeper early slope, so EDT < T30.

**What the energy parameters mean.** C50 and D50 are the same measurement in two
units, tied by $C_{50} = 10\lg[D_{50}/(1-D_{50})]$; the printed pair above
satisfies it, since $D_{50}$ = 0.499 gives $C_{50}$ = −0.02 dB, so a speech
space aiming at $D_{50} > 0.5$ is aiming at $C_{50} > 0$ dB, and there is no
point quoting both as if they were independent evidence. For music, C80 in
unoccupied concert and multi-purpose halls up to 25 000 m³ typically runs
between −5 dB and +5 dB (the "typical range" column of ISO 3382-1 Table A.1),
with negative values reading as blended or reverberant and values above about
+3 dB as dry; $T_\mathrm{S}$ in the same halls runs between 60 ms and 260 ms and moves
inversely with clarity, and $D_{50}$ between 0.3 and 0.7. Two cautions go with
those ranges. They are single-position values in *unoccupied* halls, and an
audience shortens the decay and raises clarity, so an occupied hall is not
described by them. And unlike T30, the energy parameters are early-energy
quantities that vary strongly from seat to seat, so a single-position value
means little: report the spatial mean with its spread (below). The JND column
sets the reporting resolution in the other direction: a 0.5 dB difference in
C80 between two designs is not a difference at all.

On a real, frequency-dependent decay the per-band `.plot()` is the working
summary of the whole measurement: the decay times as grouped bars per octave
(invalid bands hatched) over a second panel with C50 and C80.

![ISO 3382 per-band parameters of a synthetic room impulse response: grouped EDT, T20 and T30 bars per octave band falling from about 1.4 s at 125 Hz to 0.7 s at 4 kHz, over a second panel where C50 and C80 rise with frequency](https://docs.jmrp.io/phonometry/media/room_parameters_bands.svg)

*A room whose reverberation time falls from 1.4 s at 125 Hz to 0.7 s at
4 kHz, the typical signature of a furnished room whose absorption grows with
frequency; clarity rises as the decay shortens.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
import numpy as np
from scipy import signal
from phonometry import room

# A synthetic room IR with a frequency-dependent decay: octave-band noise
# carriers whose T60 falls from 1.4 s at 125 Hz to 0.7 s at 4 kHz.
fs = 48000
rng = np.random.default_rng(3382)
t = np.arange(int(1.6 * fs)) / fs
ir = np.zeros_like(t)
for fc, t60 in [(125.0, 1.4), (250.0, 1.25), (500.0, 1.1),
                (1000.0, 1.0), (2000.0, 0.85), (4000.0, 0.7)]:
    sos = signal.butter(4, [fc / np.sqrt(2), fc * np.sqrt(2)],
                        btype="bandpass", fs=fs, output="sos")
    carrier = signal.sosfilt(sos, rng.standard_normal(t.size))
    ir += carrier * np.exp(-3.0 * np.log(10.0) / t60 * t)

# One line: per-band EDT/T20/T30 bars + C50/C80 (needs matplotlib).
octaves = room.room_parameters(ir, fs)
octaves.plot()
plt.show()

# By hand: the T30 spectrum from the result's fields.
fig, ax = plt.subplots()
ax.bar(np.arange(octaves.t30.size), octaves.t30)
ax.set_xticks(np.arange(octaves.t30.size))
ax.set_xticklabels([f"{f:g}" for f in octaves.frequencies])
ax.set_xlabel("Octave-band centre frequency [Hz]")
ax.set_ylabel("T30 [s]")
plt.show()
```

### Reading EDT, T20 and T30 against each other

The three times extrapolate the same 60 dB decay from different windows, so
their disagreement carries information:

- **T20 ≈ T30** (curvature below 10 %): the decay is close to a single
  straight slope over both evaluation windows, which is consistent with
  (though not proof of) a diffuse field, and either time can stand for
  "the" reverberation time of the band.
- **T30 > T20** (curvature above 10 %): the decay sags, with late energy
  decaying more slowly than early energy. The usual causes are coupled
  volumes (an open door to a corridor or stairwell, a deep balcony or a
  stage house feeding energy back) and strongly uneven absorption that
  leaves one room axis reverberant. No single number describes such a
  decay: report both windows together with the curvature, and treat the
  [statistical predictions](https://docs.jmrp.io/phonometry/buildings/rooms/reverberation-prediction/)
  with suspicion, because their diffuse-field assumption has visibly
  failed.
- **EDT far from T20/T30**: EDT is fitted where the direct sound and the
  first reflections still dominate, so it varies from seat to seat while
  T30 barely moves. EDT below T30 means the position receives strong early
  energy (close to the source, under a reflector): the room sounds drier
  there than its T30 suggests, because perceived reverberance follows EDT.
  EDT above T30 at one seat points to an echo or a focusing surface
  concentrating late energy there.

The three cases are three shapes, and they are worth seeing side by side before
you have to diagnose one.

![Three panels sharing a level axis, each a Schroeder decay curve of a synthetic impulse response with its EDT, T20, T30 and curvature printed: a straight single-slope decay with curvature near zero, a sagging two-exponential decay with a visible knee and curvature well above ten per cent, and a decay preceded by a strong direct sound and one early reflection whose early decay time falls far below the T30](https://docs.jmrp.io/phonometry/media/decay_signatures.svg)

*Three decays, one axis, all read by `room_parameters`. Left, a single
exponential at $T$ = 1.0 s: EDT, T20 and T30 all return 1.00 s and the curvature
is −0.1 %. Middle, a coupled volume: 98 % of the energy decaying at 0.6 s over
a 2.5 s tail, which puts a visible knee in the Schroeder curve and returns
EDT 0.72 s, T20 1.78 s, T30 2.18 s and a curvature of **23 %**: no single number
describes it. Right, the same 1.0 s tail preceded by a cluster of strong early
reflections in the first 25 ms: T20 and T30 are untouched at 0.99 s and 1.00 s,
the curvature stays at 0.5 %, and **EDT collapses to 0.58 s**: the seat sounds
drier than its reverberation time says, and only EDT knows.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
# `np`, `fs` and `room` are the imports of the decay block above.

rng = np.random.default_rng(3382)
span = np.arange(int(4.0 * fs)) / fs


def energy(t60):                       # the p^2 envelope of a T60 = t60 decay
    return np.exp(-6.0 * np.log(10.0) / t60 * span)


noise = rng.standard_normal(span.size)
tail = noise * np.sqrt(energy(1.0))

early = tail.copy()                    # a cluster of strong early reflections
amplitude = np.sqrt(6.0 * float(np.sum(tail ** 2)) / 8.0)
for k, i in enumerate(np.linspace(0, int(0.025 * fs), 8).astype(int)):
    early[i] += amplitude * 0.85 ** k * (1.0 if k % 2 == 0 else -1.0)

cases = {
    "single slope": tail,
    "coupled volume": noise * np.sqrt(0.98 * energy(0.6) + 0.02 * energy(2.5)),
    "strong early energy": early,
}
fig, axes = plt.subplots(1, 3, sharey=True, figsize=(13.0, 4.4))
for ax, (name, signal) in zip(axes, cases.items()):
    res = room.room_parameters(signal, fs, limits=None)
    room.decay_curve(signal, fs).plot(ax=ax)
    ax.set_title(f"{name}\nEDT {res.edt[0]:.2f}  T20 {res.t20[0]:.2f}  "
                 f"T30 {res.t30[0]:.2f}  C {res.curvature[0]:.0f} %")
plt.show()
```

### How much decay range the noise floor allows

A fit window is only as good as
the decay range underneath it. The **impulse-to-noise ratio** (INR) is the
level distance between the peak of the band-filtered IR and its noise
floor; the fit window plus a safety margin must fit inside it, which is the
ISO 3382 requirement of at least 35 dB of usable decay range for T20 and
45 dB for T30. An undersized range biases the fitted time upward, toward
the flat tail the noise floor imposes on the decay curve, and the bias
grows quietly before the fit visibly fails (Hak, Wenmaekers, & van
Luxemburg, 2012). `room_parameters` reports that INR per band as
`dynamic_range` and tightens the acceptance limits to 46 dB (T20) and 54 dB
(T30) before
flagging a value valid, so the residual truncation-and-compensation bias of
a flagged-valid time stays inside 5 %: the relative JND Table A.1 tabulates
for EDT and the value customarily applied to T20 and T30, for which the table
gives none. When a band fails its flag,
the order of remedies is: use T20 instead of T30 (its window needs 10 dB
less range under the ISO minima, 8 dB under the tightened flags); raise the
INR at acquisition, since doubling the sweep length or
the number of synchronous averages buys 3 dB each time; and only then fall
back to EDT, never to a fit stretched into the noise.

**Where the noise floor comes from, and how to lose it.** The background level
is estimated from the **last tenth** of the onset-trimmed response, so the
recording must actually contain the room's steady background *after* the decay
has finished (half a second or more of it). A file trimmed to the audible decay,
or a `length=` set to the decay alone, makes the analyser measure decaying
signal as if it were noise: the estimated floor sits too high, the truncation
point moves earlier, the compensated tail is computed from the wrong crossing,
and the per-band validity flags are applied to a fictitious dynamic range, all
without an error or a warning. Record silence after the excitation (the same
silence ISO 18233 6.2.2.3 asks for), keep it in the file, and let
`room_parameters` find the crossing rather than trimming to taste. The
diagnostic for the mistake: an implausibly large `dynamic_range` on a band that
should be noisy, together with a curvature near zero, is the signature of a
missing noise tail.

The whole budget fits in one drawing, and so does the bias it controls.

![Level against time for one band-filtered impulse response: the peak at 0 dB, the squared impulse response falling as a straight line, a horizontal background-noise plateau at minus 55 decibels, a vertical bracket between the two labelled INR, the crossing of the fitted line with the noise estimate marked as the truncation point with the region beyond shaded as the compensated tail, and on the right a stacked ruler of the EDT, T20 and T30 evaluation windows each with a hatched 15 decibel margin extension and the 46 and 54 decibel flag thresholds marked against the INR bracket](https://docs.jmrp.io/phonometry/media/diagram_decay_range.svg)

*The level budget of one band. The INR is the whole vertical space you have; the
evaluation window plus the 15 dB margin of ISO 3382-1 clause 5.3.3 has to fit
inside it, which is where 35 dB (T20) and 45 dB (T30) come from. The
integration stops where the fitted line crosses the background estimate, and the
tail beyond is replaced by the exponential continuation of the fit, a
compensation whose residual bias is positive, which is why phonometry adds a
further 11 dB and 9 dB of headroom before it calls a band valid.*

![Percentage error of the fitted T20 and T30 against the returned dynamic range from 25 to 80 decibels for a synthetic one second decay: both errors are positive and grow as the dynamic range shrinks, T30 leaving the shaded plus or minus five per cent band below about 54 decibels and T20 below about 46 decibels, with vertical markers at the ISO minima of 35 and 45 decibels and the flagged-invalid region hatched](https://docs.jmrp.io/phonometry/media/decay_range_bias.svg)

*A synthetic $T$ = 1.0 s decay with its noise floor swept, measured with
`room_parameters`. The bias is always **positive**: the flat noise tail can
only make the fitted decay look longer, and it grows as the range shrinks:
+0.4 % at 70 dB, +1.3 % (T30) at 61 dB, +3.1 % at 55 dB, +6.6 % at 46 dB and
+8.8 % for T20 at 37 dB, just above the ISO minimum. That is the whole argument
for the tightened flags: at ISO's own 35 dB and 45 dB minima the surviving bias
is already outside the 5 % JND, and only at 46 dB and 54 dB does it fall inside.
Below about 34 dB the fit does not converge at all and the parameters return
NaN, which is the visible failure the bias creeps up on.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
# `np`, `fs` and `room` are the imports of the decay block above.

rng = np.random.default_rng(3382)
grid = np.arange(int(3.0 * fs)) / fs
clean = rng.standard_normal(grid.size) * np.exp(-3.0 * np.log(10.0) * grid)
noise = rng.standard_normal(grid.size)
peak = float(np.max(np.abs(clean)))

ranges, bias20, bias30 = [], [], []
for inr in range(25, 81, 3):
    res = room.room_parameters(clean + noise * peak * 10 ** (-inr / 20.0),
                               fs, limits=None)
    ranges.append(float(res.dynamic_range[0]))
    bias20.append(100.0 * (float(res.t20[0]) - 1.0))
    bias30.append(100.0 * (float(res.t30[0]) - 1.0))

fig, ax = plt.subplots()
ax.plot(ranges, bias20, "-o", label="T20")
ax.plot(ranges, bias30, "-s", label="T30")
ax.axhspan(-5.0, 5.0, alpha=0.15)
for limit, name in ((35.0, "ISO T20"), (45.0, "ISO T30"),
                    (46.0, "flag T20"), (54.0, "flag T30")):
    ax.axvline(limit, ls=":", alpha=0.6)
ax.set_xlabel("dynamic_range (INR) [dB]")
ax.set_ylabel("Error of the fitted decay time [%]")
ax.legend()
plt.show()
```

### Below the Schroeder frequency: modes, not decay

Below the **Schroeder frequency**
$f_\mathrm{s} \approx 2000\sqrt{T/V}$ ($V$ in m³, $T$ in s) these
decay statistics stop telling the whole story: the field is ruled by
discrete **room modes**. The constant is not a physical one. Each mode damped to
a reverberation time $T$ has a half-power bandwidth of about $2.2/T$ hertz, the
modal density grows as $4\pi Vf^2/c_0^3$, and requiring roughly three modes
inside one bandwidth gives $2000\sqrt{T/V}$: a *choice* of how much overlap
counts as diffuse, which is why stricter texts quote 4000 for the same physics.
The transition is soft, so a band straddling $f_\mathrm{s}$ should be checked position by
position rather than trusted, and the
[mode ladder](https://docs.jmrp.io/phonometry/buildings/rooms/room-image-sources/#3-modes-of-a-rectangular-room)
of the image-sources guide enumerates what is actually down there. The
simulation below drives the same rigid
5 m by 3.5 m room at its (2,1) mode and then between two modes; on
resonance a standing-wave pattern with fixed nodal lines grows until it
dominates the RMS pressure map, off resonance the room still responds,
but the forced field stays weak and never organises into that (2,1)
nodal pattern.

**Video:** [On-mode versus off-mode drive in a rigid room (2D FDTD)](https://docs.jmrp.io/phonometry/media/anim_fdtd_room_modes.webm): A 2D FDTD simulation of a rigid 5 by 3.5 metre room driven at the 84 Hz (2,1) mode and at an off-mode frequency side by side. On resonance a standing-wave pattern with fixed nodal lines grows until it dominates the RMS pressure map; off resonance the forced response stays weak and never organises into that nodal structure.

### `room_parameters()` parameters

| Parameter | Type | Units | Range / default | Notes |
| :--- | :--- | :--- | :--- | :--- |
| `ir` | 1D array | any | non-silent | Measured impulse response |
| `fs` | int | Hz | > 0 | Sample rate |
| `limits` | (float, float) or `None` | Hz | default `(125.0, 4000.0)` | Band-centre limits; `None` = broadband single band |
| `fraction` | int | — | `1` (octave, default) / `3` (third) | Bandwidth fraction |
| `zero_phase` | bool | — | default `False` | Forward-backward octave filtering (ISO 3382-2 §7.3 NOTE, which relaxes $B\,T > 16$ to $B\,T > 4$); removes the filter group delay before the backward integration and roughly halves the 125 Hz short-decay T30 bias (~+4.9 % → +2.4 % at $T$ = 0.2 s). `decay_curve` accepts it too |

$B\,T$ is the **bandwidth-time product**: $B$ the bandwidth of the analysis band
in hertz and $T$ the reverberation time in that band, in seconds. The two
symbols in that cell are not the same $T$ as the filter's: "$T$ = 0.2 s" means
the reverberation time. The 125 Hz octave is about 88 Hz wide, so a 0.2 s decay
gives $B\,T \approx 18$ and only just clears the ISO 3382-2 §7.3 threshold of
16; halve the decay or move to third octaves and it does not, which is the
regime the NOTE's relaxation exists for.

Returns a `RoomAcousticsResult`: `frequencies` (band centres, or `None`
broadband), `edt`/`t20`/`t30` (s), `c50`/`c80` (dB), `d50`, `ts` (s),
`dynamic_range` (dB, the per-band INR: band-filtered peak minus noise floor),
the `edt_valid`/`t20_valid`/`t30_valid` flags (ISO
3382-1 §5.3.3: noise ≥ 25 dB below the peak for EDT, tightened to 46 dB for
T20 and 54 dB for T30 so the tail-compensation bias of a flagged-valid value
stays within the 5 % JND) and `curvature`
$C = 100\ (T_{30}/T_{20} - 1)$ % (values above 10 % flag a non-straight
decay). `decay_curve(ir, fs, band=None, fraction=1, zero_phase=False)` returns
just the decay curve for one band or the broadband response, a `DecayCurve`
read by name as `.times` and `.levels`.

### Averaging over positions

Everything above analyses one impulse response; a reported room parameter is
never one impulse response. ISO 3382-2 clause 8 gives two admissible procedures,
and the one this API supports is the first: the **arithmetic mean of the
individual reverberation times over all independent source-microphone
combinations** (the alternative, ensemble-averaging the decay curves themselves
with their beginnings synchronised, is a different operation and is not what
averaging `t30` does). Four rules travel with it. The standard deviation across
positions is part of the answer, not a diagnostic afterthought, and should be
quoted whenever it exceeds the parameter's JND. $T_\text{mid}$, the customary
single-number room descriptor, is the mean of the 500 Hz and 1 kHz octaves. The
energy parameters vary far more between seats than T30 does, so their spread is
the interesting number rather than a nuisance. And a band that fails its
validity flag at some positions must not be quietly averaged in: mask it, and
say how many positions survived.

```python
# `np`, `fs` and `room` are the imports of the decay block above.

# measured: one impulse response per source-microphone combination. Three
# synthetic decays of 0.95, 1.00 and 1.08 s stand in for three positions.
rng = np.random.default_rng(3382)
grid = np.arange(int(3.0 * fs)) / fs
responses = [rng.standard_normal(grid.size) * np.exp(-3.0 * np.log(10.0) / t60 * grid)
             for t60 in (0.95, 1.00, 1.08)]

results = [room.room_parameters(each, fs) for each in responses]
t30 = np.array([res.t30 for res in results])
valid = np.array([res.t30_valid for res in results])

mean = np.nanmean(np.where(valid, t30, np.nan), axis=0)
spread = np.nanstd(np.where(valid, t30, np.nan), axis=0)
print(np.round(mean, 2))                  # [0.98 1.   1.02 1.02 1.03 1.01] s
print(np.round(100.0 * spread / mean, 1))  # [4.5 4.3 4.8 5.1 4.9 4.8] %
print(int(valid.sum(axis=0).min()))        # 3 positions survived the flag
```

Here the spread runs 4 to 5 %, right at the JND, so it belongs in the report
beside the mean: three positions that agree to 5 % are three positions that
disagree audibly. Note also what the mask is for: `np.nanmean` over the masked
array is the arithmetic mean clause 8 a) prescribes, but only over the
combinations whose band actually passed, and the surviving count is part of the
result.

### A measured chapel against its published parameters

Everything above runs on synthetic decays. The repository also keeps a real
one: the impulse response of the St. Nicholas Chapel of Aachen Cathedral, a
coupled Gothic chapel of about 3050 m³ that FH Aachen measured to
ISO 3382-1 with a dodecahedral source and an exponential sweep, source 1 and
receiver 1 standing 2.56 m apart. The deposit publishes the room parameters
its authors computed with their own software, per one-third-octave band, so
the same response can be run through `room_parameters` and set against them.
The yardstick is the one ISO 3382-1 gives for whether two values of a
parameter differ audibly: the just noticeable differences (JND) of Table A.1,
5 % of the value for EDT, 1 dB for C80, 0.05 for D50 and 10 ms for the
centre time Ts, which `room.TABLE_A1` holds.

**The data.** Omnidirectional channel of the S1-Do_R1 impulse response from
M. Zerwas and S. Kayku, 'Room acoustic measurement and decay analysis data of
the St. Nicholas Chapel, Aachen Cathedral', Zenodo, 2026, DOI
[10.5281/zenodo.20428705](https://doi.org/10.5281/zenodo.20428705), licensed
[CC BY 4.0](https://creativecommons.org/licenses/by/4.0/). Change: one channel
of four extracted and repackaged.

The file is read from a checkout of the repository, where the oracle test
reads it too; a wheel does not install the test data.

```python
import pathlib

import numpy as np
import phonometry
from phonometry import room

# The committed response lives in the repository, so this runs from a checkout
#   (or an editable install); with your own measured response, load that instead.
repo = pathlib.Path(phonometry.__file__).resolve().parents[2]
with np.load(repo / "tests/data/audio/nikolauskapelle/s1_do_r1_w.npz") as npz:
    chapel_ir, chapel_fs = npz["w"].astype(np.float64), int(npz["fs"])

chapel = room.room_parameters(chapel_ir, chapel_fs, limits=(100.0, 5000.0), fraction=3)
bands = [100, 125, 160, 200, 250, 315, 400, 500, 630, 800,
         1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000]

# The deposit's workbook, row S1-Do_R1, one value per band from 100 Hz to 5 kHz.
published = {
    "EDT": [3.3121, 3.4835, 4.6281, 4.2371, 4.3389, 3.8817, 3.6988, 3.8547, 4.4786,
            4.9678, 3.8599, 3.4878, 2.5415, 2.6911, 2.2371, 1.7814, 1.4736, 1.198],
    "T20": [4.3325, 4.4211, 4.2996, 4.7631, 4.944, 4.9925, 4.7133, 4.7381, 4.649,
            4.5321, 4.533, 4.1439, 3.8006, 3.3868, 2.8327, 2.4767, 1.9659, 1.5017],
    "T30": [4.7058, 4.7348, 4.4475, 4.6511, 4.6734, 4.8526, 4.7217, 4.8584, 4.7744,
            4.6152, 4.4409, 4.1049, 3.8218, 3.3945, 2.9959, 2.4781, 2.0283, 1.5823],
    "C50": [-0.8857, -1.6775, -1.1019, -0.8407, -2.4858, -1.0162, 0.0553, -0.7639,
            -2.097, 0.0628, -1.4394, 0.3681, 1.4292, 1.7993, 1.1941, 1.1194, 2.5834, 4.6042],
    "C80": [-0.36, -0.8159, -1.2315, -0.1926, -1.8477, 0.7525, 0.9272, -0.171, -1.5149,
            0.9836, 0.023, 1.7805, 2.8353, 3.2893, 3.2199, 2.5758, 4.344, 6.177],
    "D50": [0.4552, 0.4075, 0.4352, 0.4514, 0.3617, 0.4439, 0.5076, 0.4519, 0.3836,
            0.5026, 0.4179, 0.5206, 0.5817, 0.602, 0.5684, 0.564, 0.6443, 0.743],
    # Ts in milliseconds, as the workbook gives it, turned into seconds.
    "Ts": [ms / 1000 for ms in (226.79, 220.39, 232.98, 189.96, 260.19, 182.72, 162.69, 202.2,
                                242.02, 213.45, 195.51, 153.0, 114.73, 104.2, 100.94, 90.64,
                                64.43, 44.36)],
}
computed = {"EDT": chapel.edt, "T20": chapel.t20, "T30": chapel.t30,
            "C50": chapel.c50, "C80": chapel.c80, "D50": chapel.d50, "Ts": chapel.ts}
print(f"T30 at 1 kHz: {chapel.t30[10]:.2f} s, published {published['T30'][10]:.2f} s")
# T30 at 1 kHz: 4.46 s, published 4.44 s

# ISO 3382-1 Table A.1 gives the just noticeable difference (JND) of EDT, C80,
#   D50 and Ts; T20, T30 and C50 have no row of their own, and the test holds
#   them to the JND of EDT (5 %) and of C80 (1 dB).
jnd_row = {"EDT": "EDT", "T20": "EDT", "T30": "EDT",
           "C50": "C80", "C80": "C80", "D50": "D50", "Ts": "Ts"}
for name, values in published.items():
    row = room.TABLE_A1[jnd_row[name]]
    gap = computed[name] - np.asarray(values)
    if row.relative_jnd:
        gap = gap / np.asarray(values)
    in_jnds = gap / row.just_noticeable_difference
    worst = int(np.argmax(np.abs(in_jnds)))
    print(f"{np.sum(np.abs(in_jnds) <= 1)} of {len(bands)} bands within one JND for {name}, "
          f"worst {in_jnds[worst]:+.1f} JND at {bands[worst]} Hz")
# 17 of 18 bands within one JND for EDT, worst +1.3 JND at 5000 Hz
# 18 of 18 bands within one JND for T20, worst +0.5 JND at 250 Hz
# 18 of 18 bands within one JND for T30, worst +0.6 JND at 250 Hz
# 17 of 18 bands within one JND for C50, worst -1.5 JND at 100 Hz
# 18 of 18 bands within one JND for C80, worst -0.9 JND at 100 Hz
# 17 of 18 bands within one JND for D50, worst -1.8 JND at 100 Hz
# 17 of 18 bands within one JND for Ts, worst +1.3 JND at 250 Hz
```

T20, T30 and C80 land on the published value within one just noticeable
difference in all 18 bands, EDT, C50, D50 and Ts in 17 of them, and T30 at
1 kHz reads 4.46 s against the published 4.44 s. The four misses are the two
edge cases
[the test](https://github.com/jmrplens/phonometry/blob/main/tests/room/test_room_nikolauskapelle_oracle.py)
documents and holds at three JNDs instead of one. EDT at 5 kHz is +1.3 JND:
air absorption shortens the decay at the top of the range, so the 0 to
−10 dB fit has very little of it to work with. And the quantities that hang
on where the response starts: the early-energy ratios at 100 Hz, C50 at
−1.5 JND and D50 at −1.8, with C80 just inside at −0.9, and the centre time
Ts at 250 Hz, +1.3 JND. At 100 Hz a one-third-octave filter's group delay is
comparable to the 50 ms and 80 ms early/late split, so where each
implementation puts the start of the response decides most of the ratio;
Ts is a time counted from that same start, so it moves with it. Two independent
implementations agreeing that closely on decays this long is as strong a
statement as the parameters' definitions allow.

![ISO 3382 per-band parameters of the St. Nicholas Chapel in one-third octaves from 100 Hz to 5 kHz: EDT, T20 and T30 bars falling from about 4.7 s to 1.5 s, each topped by an open marker at the value the deposit publishes, over a second panel where the computed C50 and C80 curves follow the published values within a decibel in every band but one, C50 at 100 Hz](https://docs.jmrp.io/phonometry/media/room_parameters_chapel.svg)

*The chapel through the result's own `.plot()`, with the deposit's published
row drawn over it as open markers. The bars and the curves are what
`room_parameters` computes from the impulse response alone; the markers are
the authors' numbers, within one just noticeable difference of the bars and
the lines in every band but the ones the prints above name.*

**Show the code for this figure**

```python
import matplotlib.pyplot as plt
import numpy as np

# `chapel`, `published` and `bands` come from the snippet above.
# One line: the result draws its own bars and curves; the published row goes on top.
ax_times, ax_clarity = chapel.plot()
x = np.arange(len(bands))
for offset, name in [(-0.27, "EDT"), (0.0, "T20"), (0.27, "T30")]:
    ax_times.plot(x + offset, published[name], "o", mfc="none", color="k",
                  label="Published" if name == "EDT" else None)
for name in ["C50", "C80"]:
    ax_clarity.plot(x, published[name], "o", mfc="none", label=f"{name} published")
ax_times.legend()
ax_clarity.legend()
plt.show()

# By hand: the decay times as bars and the clarities as lines, the published
# row as open markers over them, from the result's fields.
fig, (top, bottom) = plt.subplots(2, 1, sharex=True)
for offset, name, values in [(-0.27, "EDT", chapel.edt), (0.0, "T20", chapel.t20),
                             (0.27, "T30", chapel.t30)]:
    top.bar(x + offset, values, width=0.27, label=name)
    top.plot(x + offset, published[name], "o", mfc="none", color="k")
for name, values in [("C50", chapel.c50), ("C80", chapel.c80)]:
    line, = bottom.plot(x, values, "o-", label=name)
    bottom.plot(x, published[name], "o", mfc="none", color=line.get_color())
bottom.set_xticks(x, [str(band) for band in bands], rotation=45)
bottom.set_xlabel("Frequency [Hz]")
top.set_ylabel("Decay time [s]")
bottom.set_ylabel("Clarity [dB]")
top.legend()
bottom.legend()
plt.show()
```

### ISO 3382 report (`.report()`)

`RoomAcousticsResult.report(path)` renders a one-page PDF fiche laid out like a
room-acoustics measurement report (a performance space per ISO 3382-1:2009 or
an ordinary room per ISO 3382-2:2008, both evaluated by the integrated
impulse-response method): a standard-basis line, an optional metadata header
block, the full-width per-band parameter table ($T_{20}$, $T_{30}$, EDT,
$C_{50}$, $C_{80}$, $D_{50}$, $T_\mathrm{S}$) above the result's own per-band
decay-time plot (`.plot()`), the boxed mid-frequency reverberation time
$T_\text{mid}$ (the mean of the 500 Hz and 1000 Hz octave $T_{30}$, the
customary room descriptor) with the mid-frequency EDT alongside, and a footer
with the fixed disclaimer. ISO 3382-1/-2 are **characterisation** standards
with no intrinsic pass/fail, so a verdict row appears only when a target
reverberation time is supplied through the metadata's `requirement` field
(`ReportMetadata(requirement=...)`, read as the maximum acceptable value of
whichever descriptor the box carries, the usual form of a classroom or
open-plan limit). A broadband result has no 500 Hz / 1000 Hz octaves to
average, so its box and verdict fall back to the plain broadband $T_{30}$ with
no "500-1000 Hz" claim, and so do a band range that misses those two octaves
and one that reaches them with a non-evaluable $T_{30}$ in either, which fall
back to the first band whose $T_{30}$ could be evaluated. It uses the same
`ReportMetadata` container and rendering engine as the [ISO 11654 absorption
fiche](https://docs.jmrp.io/phonometry/materials/absorbers/absorption-measurement/#iso-11654-report-report);
the room-specific fields `room_volume`, `n_source_positions` and
`n_receiver_positions` populate the header (ISO 3382 requires the room volume and
the number of source and microphone positions to be reported), alongside
`test_room` (the room name), `specimen` (the room description and occupancy
state), `area`, `instrumentation`, `temperature_c`,
`relative_humidity_percent`, `static_pressure_kpa`, `measurement_standard`,
`test_date`, `laboratory`, `operator`, `report_id` and `notes`. Passing
`metadata=None` produces a bare characterisation fiche. Rendering needs
reportlab and, for the figure the fiche embeds, matplotlib (`pip install
"phonometry[report,plot]"`); only `engine="reportlab"` is supported. The fiche
renders in English by default; pass `language="es"` for a Spanish fiche
(translated fixed strings and a comma decimal separator).

```python
from phonometry import room, ReportMetadata

result = room.room_parameters(ir, fs)   # octave bands 125 Hz - 4 kHz
result.report(
    "room_fiche.pdf",
    metadata=ReportMetadata(
        # The room condition clause 9.2 e) asks for: furnishing state and the
        # number of persons present (clause 4.1 allows at most two to stand in
        # for the unoccupied state).
        specimen="Small auditorium, fully furnished, unoccupied (1 operator present)",
        test_room="Auditorium A",
        room_volume=2830.0, area=340.0,
        n_source_positions=2, n_receiver_positions=8,
        # Clause 9.2 i) requires the accuracy grade to be stated.
        measurement_standard="ISO 3382-2 (engineering grade)",
        temperature_c=21.0, relative_humidity_percent=45.0,
        laboratory="Phonometry Reference Laboratory",
        notes="16 source-microphone combinations, 2 decays each; "
              "positions and heights on the attached scaled plan",
        requirement=1.3,           # adds a verdict against a target T_mid
    ),
)                                  # T_mid + the per-band parameter table
```

Three of those entries are there because ISO 3382-2 clause 9.2 asks for them and
the fiche has no dedicated field for any of them. Clause 9.2 i) requires the
**degree of precision** (survey, engineering or precision), so it belongs in
`measurement_standard` rather than being left implied. Clause 9.2 e) requires
the **condition of the room**, furnishing and the number of persons present, and
clause 4.1 fixes what "unoccupied" may mean: no people, or at most two allowed
to stand in for the unoccupied state unless otherwise specified; that goes in
`specimen`. And clause 9.2 c) and i) together require a **scaled sketch plan**
carrying the source and microphone positions with their heights, which the fiche
does not draw: produce it alongside and reference it, as `notes` does here.
Clause 9.2 f) adds the temperature and relative humidity for the precision
method only, which the climate fields already carry.

The example fiche is regenerated with `make reports` and kept rendered in the
repository; click the preview to open the PDF.

**Report:** [ISO 3382 room acoustic parameters example report (PDF)](https://docs.jmrp.io/phonometry/media/iso3382_room_acoustics_example.pdf): One-page room-acoustics fiche: a metadata header (client, room, description, room volume, floor area, source and microphone positions, instrumentation, temperature, humidity and pressure), the octave-band parameter table (T20, T30, EDT, C50, C80, D50 and Ts from 125 Hz to 4 kHz) above the per-band decay-time bar plot, the boxed mid-frequency reverberation time T_mid = 1.15 s with the mid-frequency EDT alongside, and a PASS verdict against the 1.3 s target.

Room acoustic parameters fiche (RoomAcousticsResult.report), T_mid and the per-band table.

With the parameters in hand, the two neighbouring links in the chain are the
acquisition that produced the impulse response
([Measuring the Room Impulse Response](https://docs.jmrp.io/phonometry/buildings/rooms/room-impulse-response/))
and, for an open-plan floor rather than a closed room, the ISO 3382-3 line of
workstations
([Open-Plan Office Acoustics](https://docs.jmrp.io/phonometry/buildings/rooms/open-plan-acoustics/)).

## What this guide covers

- **Covered.** ISO 3382-1:2009 (clause 5.3.3 backward integration and the Annex A parameter
  formulae) and ISO 3382-2:2008 (Clause 6 and the 5.3.3 dynamic-range
  criterion), computed by `room.room_parameters`/`room.decay_curve`: EDT, T20,
  T30, C50, C80, D50, Ts and the per-band validity and curvature flags, with the
  optional zero-phase band filtering of the ISO 3382-2 §7.3 NOTE, and the
  one-page ISO 3382 fiche through `.report()`.

- **Not covered.** ISO 3382-1 Annex A also defines the sound-strength $G$ and the binaural
  parameters LF/LFC and IACC; phonometry implements only the reverberance and
  clarity family named above (EDT, T20, T30, C50, C80, D50, Ts). The acquisition
  of the impulse response (ISO 18233) and the open-plan quantities (ISO 3382-3)
  have guides of their own, [Measuring the Room Impulse
  Response](https://docs.jmrp.io/phonometry/buildings/rooms/room-impulse-response/) and [Open-Plan
  Office Acoustics](https://docs.jmrp.io/phonometry/buildings/rooms/open-plan-acoustics/). The ISO
  354 reverberation-room absorption that consumes the measured $T_1$/$T_2$ pair
  lives in [Sound Absorption Measurement and
  Rating](https://docs.jmrp.io/phonometry/materials/absorbers/absorption-measurement/).

## See also

- [Measuring the Room Impulse Response](https://docs.jmrp.io/phonometry/buildings/rooms/room-impulse-response/):
  the ISO 18233 acquisition of the IR this page analyses.
- [Open-Plan Office Acoustics (ISO 3382-3)](https://docs.jmrp.io/phonometry/buildings/rooms/open-plan-acoustics/):
  the speech-privacy quantities of open-plan offices.
- [Sound Absorption Measurement and Rating](https://docs.jmrp.io/phonometry/materials/absorbers/absorption-measurement/):
  the ISO 354 reverberation-room absorption measurement that consumes the
  reverberation times `room_parameters` returns, and its ISO 11654 rating.
- [Field](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-field/),
  [laboratory](https://docs.jmrp.io/phonometry/buildings/insulation/insulation-lab/) and
  [predicted](https://docs.jmrp.io/phonometry/buildings/design/insulation-prediction/) sound insulation: field,
  laboratory and predicted sound insulation between spaces, and its measurement uncertainty.
- [Sound Power](https://docs.jmrp.io/phonometry/devices/emission/sound-power/): the $L_W$ methods that consume the
  ISO 354 absorption area (the ISO 3744 $K_2$ and the ISO 3741 absorption term).
- [Loudness](https://docs.jmrp.io/phonometry/perception/psychoacoustics/loudness/) and
  [Sound Quality Metrics](https://docs.jmrp.io/phonometry/perception/psychoacoustics/sound-quality/): loudness, sharpness and the other
  perception metrics of what the room delivers.
- [Filter Banks](https://docs.jmrp.io/phonometry/signals/filters/filter-banks/): the IEC 61260 fractional-octave filters
  used for band decay curves and insulation spectra.
- [Theory](https://docs.jmrp.io/phonometry/reference/theory/rooms-buildings/): Schroeder integration, regression windows and the
  reference-curve derivation.
- [Conformance report](https://docs.jmrp.io/phonometry/reference/conformance/): the closed-form decays and parameter
  definitions the ISO 3382 implementations are validated against.
- API reference: [`room.acoustics`](https://docs.jmrp.io/phonometry/reference/api/rooms/acoustics/).
- Theory: [Impulse response and room-acoustic parameters](https://docs.jmrp.io/phonometry/reference/theory/rooms-buildings/#impulse-response-and-room-acoustic-parameters-iso-18233-iso-3382-1-2-3): the decay model behind T20, T30 and EDT and the energy ratios the clarity and definition parameters are built from.

## Quick answers

### How are EDT, T20 and T30 defined?

Each band of the impulse response is turned into a decay curve by Schroeder backward integration of the squared IR, and a least-squares line fitted over an evaluation range is extrapolated to a full 60 dB drop, $T = -60/\text{slope}$ (ISO 3382-1/2): EDT over 0 to −10 dB (perceived reverberance), T20 over −5 to −25 dB and T30 over −5 to −35 dB.

### How much decay range do I need for a valid T20 or T30?

The fit window plus a safety margin must fit inside the impulse-to-noise ratio (`res.dynamic_range`), the level distance between the band-filtered IR peak and its noise floor: ISO 3382 requires at least 35 dB of usable decay range for T20 and 45 dB for T30. An undersized range biases the fitted time upward, so `room_parameters` tightens its validity flags to 46 dB and 54 dB, keeping the bias inside the 5 % JND. The noise floor is estimated from the last tenth of the response, so the recording must contain silence after the decay.

## References

- **Hak, C. C. J. M., Wenmaekers, R. H. C., & van Luxemburg, L. C. J. (2012).** Measuring room impulse responses: Impact of the decay range on derived room acoustic parameters. *Acta Acustica united with Acustica*, *98*(6), 907-915. https://doi.org/10.3813/aaa.918574
  The INR analysis behind the dynamic-range discussion and the tightened validity flags of this page.
- **International Organization for Standardization. (2008).** [*Acoustics — Measurement of room acoustic parameters — Part 2: Reverberation time in ordinary rooms*](https://www.iso.org/standard/36201.html) (ISO 3382-2:2008).
  The accuracy grades and the dynamic-range criterion behind the decay analysis; its position rules are applied in the room-impulse-response guide.
- **International Organization for Standardization. (2009).** [*Acoustics — Measurement of room acoustic parameters — Part 1: Performance spaces*](https://www.iso.org/standard/40979.html) (ISO 3382-1:2009).
  The parameter definitions and just-noticeable differences behind the decay analysis.
- **Kuttruff, H. (2016).** *Room acoustics* (6th ed.). CRC Press. https://doi.org/10.1201/9781315372150
  The reference monograph behind this page: the statistical theory of decaying sound fields, the Schroeder frequency and the perceptual room parameters of this page.
- **Schroeder, M. R. (1965).** New method of measuring reverberation time. *The Journal of the Acoustical Society of America*, *37*(3), 409-412. https://doi.org/10.1121/1.1909343
  The backward-integration method that turns the squared impulse response into the smooth decay curve of this page.
- **Zerwas, M., & Kayku, S. (2026).** [*Room acoustic measurement and decay analysis data of the St. Nicholas Chapel, Aachen Cathedral*](https://zenodo.org/records/20428705) \[Data set\]. Zenodo. https://doi.org/10.5281/zenodo.20428705
  The measured chapel of the worked case: the impulse response of source 1 and receiver 1, whose omnidirectional channel the repository keeps, and the per-band parameters its authors published.